HX7+ ASD Installation and Operation Manual
73
Frequency Mode #1
Program
Fundamentals
Standard Mode Selection
The
Frequency Mode #1
setting establishes the source of the frequency-control
input for the ASD. The
Override
feature may supersede the
Frequency
Mode #1
Command Mode and Frequency Mode Control on pg. 46
Note:
Only
Bolded
items from the
Settings
list below may be placed in
the
Override
mode. See the section titled
Frequency Mode Control on pg. 46
for further information on the
Override
feature.
Settings:
1 —
Use VI/II
2 — Use RR
3 — Use RX
4 — Use Option Card RX2
5 —
Use
CN8 Option (LED Keypad)
6 — Use Binary/BCD Input
7 —
Use Common Serial (TTL)
8 —
Use RS232/RS485
9 —
Use Communication Card
10 — Use Motorized Pot. Simulation
11 — Use Pulse Input Option
Direct Access Number — F004
Parameter Type —
Selection List
Factory Default —
Use RR
Changeable During Run —
No
FM Terminal Assignment
Program
Meter Terminal Adjustment
This setting determines the output function of the
FM
analog output terminal.
The
FM
output terminal produces an output current that is proportional to the
magnitude of the function assigned to this terminal.
The available assignments for this output terminal are listed in
.
Note:
Current
is read by connecting an ammeter from FM (+) to
FM (-) via a series 100 – 500
resistor.
To read
voltage
at this terminal a 100 – 500
resistor is
required and it must be connected from FM (+) to FM (-).
The voltage is read across the 100 – 500
resistor.
The
FM
analog output has a maximum resolution of 1/1024. The
FM Terminal
Adjustment
) must be used to calibrate the output signal for a proper
response.
SW-2
may be switched to allow for the full-range output to be either
0 – 1 mA or 4 – 20 mA when measuring an output current, or either 0 – 1 or 1 –
7.5 volts when measuring an output voltage at this terminal.
Direct Access Number — F005
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...