HX7+ ASD Installation and Operation Manual
169
Emergency Off DC Injection Application Time
Program
Protection
Emergency Off
When
DC Injection
is used as a function of receiving an
Emergency Off
command
(
), this parameter determines the time that the
DC Injection
braking is applied to the motor.
Direct Access Number — F604
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Output Phase Loss Detection
Program
Protection
Phase Loss
This parameter
Enables/Disables
the monitoring of each phase of the 3-phase
output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not
of the specified level, the ASD incurs a trip.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F605
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
OL Reduction Starting Frequency
Program
Protection
Overload
This parameter is used to reduce the start frequency during very low-speed
motor operation. During very low-speed operation the cooling efficiency of the
motor decreases. Lowering the start frequency aides in minimizing the
generated heat.
Direct Access Number — F606
Parameter Type —
Numerical
Factory Default —
6.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Motor 150% OL Time Limit
Program
Protection
Overload
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
Direct Access Number — F607
Parameter Type —
Numerical
Factory Default —
600
Changeable During Run —
Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Inrush Current Suppression
Program
Protection
Soft Start
The startup inrush current may be suppressed for up to 2.5 seconds. This
parameter determines the length of the inrush current suppression.
Direct Access Number — F608
Parameter Type —
Numerical
Factory Default —
0.30
Changeable During Run —
No
Minimum — 0.30
Maximum — 2.50
Units — Seconds
Interlock with ST
Program
Protection
Soft Start
This parameter
Enables/Disables
the
ST
-to-
CC
connection dependency on the
successful completion of a
Soft Start
. If enabled, the
ST
-to-
CC
connection will
happen only after a successful
Soft Start
.
Direct Access Number — F609
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...