134
HX7+ ASD Installation and Operation Manual
At-Frequency Powerline Switching
Program
Terminal Selection
Line Power Switching
When enabled (
), this parameter sets the frequency at which the
At
Frequency Powerline Switching
function engages. The
At Frequency
Powerline Switching
function commands the system to discontinue using the
output of the drive and to switch to commercial power once reaching the
frequency set here.
Direct Access Number — F355
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
ASD-Side Switching Wait Time
Program
Terminal Selection
Line Power Switching
This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.
Direct Access Number — F356
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Commercial Power Wait Time
Program
Terminal Selection
Line Power Switching
This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
Direct Access Number — F357
Parameter Type —
Numerical
Factory Default —
0.62
Changeable During Run —
Yes
Minimum — (ASD dependent)
Maximum — 10.00
Units — Seconds
Commercial Power Switching Freq. Hold Time
Program
Terminal Selection
Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.
Direct Access Number — F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...