84
HX7+ ASD Installation and Operation Manual
Motorized Pot Frequency at Power Down
Program
Frequency Setting
Motorized Pot
When the
Frequency Mode #1 Selection
(
) setting is set to
Use MOP
Function Simulation
, this parameter determines the outcome of the
Frequency
Mode #1
setting at powerdown or stop.
Settings:
0 — Erase
1 — Store
If
Erase
is selected, the ASD will
not
store the frequency setpoint and
establishes a setpoint of 0.0 Hz when restarted.
If
Store
is selected, the ASD will maintain the current frequency setpoint in
memory while stopped, during fault conditions, or when power is removed.
This setpoint will be used as the initial frequency setpoint when the ASD is
restarted.
A control terminal configured as
MOP Frequency Clear
will establish a
frequency setpoint of 0.0 Hz regardless of the
Motorized Pot Frequency at
Power Down
setting.
Direct Access Number — F108
Parameter Type —
Selection List
Factory Default —
Erase
Changeable During Run —
No
ON Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the virtual input terminal
ON
. As a
virtual terminal, the
ON
control terminal exists only in memory and is
considered to always be in its
True
(or connected to
CC
) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to 1 of the 68 possible
Direct Access Number — F110
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
F Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
F
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
F
terminal to 1 of the 68 possible
Direct Access Number — F111
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
R Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
R
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
R
terminal to 1 of the 68 possible
Direct Access Number — F112
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...