HX7+ ASD Installation and Operation Manual
83
Input Terminal Priority
Program
Terminal Selection
Input Special
This parameter is used to allow the
Jog
and
DC Injection Braking
input
signals to control the ASD when received via the
Terminal Board
even though
the system is in the
Local
mode.
With this parameter enabled
,
a
Jog
command or a
DC Injection Braking
command received from the
Terminal Board
will receive priority over
commands from the keypad.
See for further information on using the
Jog
function.
See
for further information on
DC Injection Braking
.
Settings:
0 — Enabled (box checked)
1 — Disabled
Direct Access Number — F106
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Extended Terminal Function
Program
Terminal Selection
Input Special
The
Extended Terminal Function
is used with the optional
ASD-Multicom
card only. This parameter defines the format of the binary or BCD data when
using the option card.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Reverse 12-Bit Binary
6 — Reverse 16-Bit Binary
7 — Reverse 3-Digit BCD
8 — Reverse 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the
Terminal Board
as binary bits 0 – 3 (
–
). The
Frequency Mode #1 Selection
) must be set to
Use Binary/BCD Input
.
For proper scaling of the binary or BCD input, parameters
–
must be
configured [
BIN Reference Point #1
,
BIN Reference #1 (frequency)
,
Bin
Reference Point #2
, and
BIN Reference #2 (frequency)
].
Direct Access Number — F107
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...