116
HX7+ ASD Installation and Operation Manual
BIN Torque Reference Setpoint #2
Program
Torque Setting
Setpoints
BIN
This parameter is used to set the gain and bias of the binary input when the
discrete input terminals are used as the control input while operating in the
Torque Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a
given binary input signal.
See
BIN Speed Reference #1
for further information on this setting.
This parameter sets
BIN
Torque Reference Setpoint #2
and is the output
torque value that is associated with setting of
BIN Speed Reference #2
while
operating in the
Torque
control mode.
Direct Access Number — F233
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.0
Maximum — 250.0
Units — %
PG Speed Reference #1
Program
Frequency Setting
Speed Reference Setpoints
PG
This parameter is used to set the gain and bias of the
PG
input terminal when a
shaft-mounted encoder is used as the feedback transducer while operating in the
Speed Control
mode.
Note:
The
and the
required for system operation using the PG input speed control.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
PG
input terminal:
•
Program
Fundamentals
Standard Mode Selection
Frequency
Mode #1
Pulse Input Option
.
•
Program
Fundamentals
Standard Mode Selection
Command
Mode
(any setting).
•
Set
PG Speed Reference #1
(
) — the input pulse count rate that
represents
PG Speed Frequency #1
.
•
Set
PG Speed Frequency #1
).
•
Set
PG Speed Reference #2
(
) — the input pulse count rate that
represents
PG Speed Frequency #2
.
•
Set
PG Speed Frequency #2
).
•
Provide a
Run
command (
F
and/or
R
).
Once set, as the
PG
pulse count rate changes, the output frequency of the ASD
will vary in accordance with the above settings.
This parameter sets
PG Speed Reference #1
and is the input pulse count rate
that is associated with the setting of
PG Speed Frequency #1
while operating
in the
Speed Control
mode.
Direct Access Number — F234
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...