146
HX7+ ASD Installation and Operation Manual
Torque Command Mode
Program
Torque Setting
Torque Speed Limit
This parameter specifies whether the torque command function is to be used in
one direction or both (F/R).
Settings:
0 — Fixed Direction
1 — F/R Permitted
Direct Access Number — F429
Parameter Type —
Selection List
Factory Default —
Fixed Direction
Changeable During Run —
No
Speed Limit (torque) Reference
Program
Torque Setting
Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets the input terminal that will be used to control the allowable
speed variance.
Settings:
0 — None
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Fixed
Direct Access Number — F430
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
Yes
Speed Limit Torque Level
Program
Torque Setting
Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets the targeted speed. The plus-or-minus value (range) for this
setting may be set at
.
Direct Access Number — F431
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Speed Limit Torque Range
Program
Torque Setting
Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets a plus-or-minus value (range) for the
Speed Limit Torque Level
).
Direct Access Number — F432
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Speed Limit Torque Recovery
Program
Torque Setting
Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets the response time of the system to torque change requirements.
Direct Access Number — F433
Parameter Type —
Numerical
Factory Default —
0.20
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...