48
HX7+ ASD Installation and Operation Manual
Command and Frequency Control Selections
Using
, the user may select a
Command
source and a source for
Frequency
control. The
default settings for
Command
and
Frequency
control are
Terminal Board
and
RR
, respectively.
To be placed into the
Override
mode, there need only be a valid signal received from one of the signal
sources. If the valid signal is received via a signal source with a higher priority, it will supersede the
command or frequency command received from another source.
The signal sources are continuously scanned to determine if any of the listed items are actively
providing an input signal.
If no activity is detected on any of the listed signal sources, the settings of
will be used
for
Command
and
Frequency
control, respectively.
Any or all of the
Command
and
Frequency
control input sources may be placed in the
Override
mode.
Placing the HX7+ ASD in the
Local
mode (Local|Remote LED on) via the keypad places the
RS232/
RS485
or the
TTL
control selections in the
Override
mode for
Command
and
Frequency
input. This
selection is further defined by the setting of Program
Communication
Communication Settings
The
Local|Remote
control
Override
feature for
Command
and
Frequency
(or either) may be enabled/
disabled at Program
Utility Parameters
Prohibition
Local|Remote Key Command
or
Frequency Override
.
Communications
may be used to place the remaining
Command
and eligible
Frequency
control input
sources in the
Override
mode. Once placed in the
Override
mode the setting is valid until it is
cancelled, the power supply is turned off, or the ASD is reset.
Command and Frequency-Control Override Hierarchy
lists the input conditions and the resulting output control source selections for Command and
Frequency control Override operation. The HX7+ ASD reads the command registers of the listed
control items from the left to the right. In the table the number 1 indicates that a valid input signal is
being active for that input source; X = Don’t care; and 0 = Override Off.
The first item to be read that has the Override feature turned on will be used for Command or Frequency
control.
Table 12. Command and Frequency Control Hierarchy.
Priority Level
1
2
3
4
5
Command/
Frequency Mode
Communication
Card
RS232/
RS485
TTL
Terminal Board
(Binary/BCD Input)
F003/F004
Communication Card
1
X
X
X
X
RS232/RS485
0
1
X
X
X
TTL
0
0
1
X
X
Terminal Board
0
0
0
1
X
F003/F004 Setting
0
0
0
0
/
Setting
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...