HX7+ ASD Installation and Operation Manual
5
Conductor Routing and Grounding
Precautions
•
Use separate metal conduits for routing the input power, output power, and control circuits.
•
A separate ground cable should be run inside the conduit with the input power, output power, and
control circuits.
•
DO NOT
connect
CC
to earth ground.
•
Use the
CC
terminal as the return for analog input terminals
VI
,
RX
, and
RR
.
•
Use the
CC
terminal as the return for output terminals
FP
,
PP
, and
P24
.
•
Use the negative terminal of the
AM
,
FM
, and
II
terminals as the return for these analog inputs.
•
Always ground the unit to prevent electrical shock and to help reduce electrical noise.
•
If the ASD is being used in an ungrounded system (floating system) or in an unsymmetrically
grounded system, the EMI filter must be disconnected or removed. The ASD may be damaged if
the EMI filter is used under either of these conditions.
•
It is the responsibility of the ASD installer/maintenance personnel to provide proper grounding and
branch circuit protection in accordance with the
NEC
and any applicable local codes.
— T h e M e t a l C o n d u i t I s N o t A n A c c e p t a b l e G r o u n d —
Power Connections Precautions
C O N T A C T W I T H E N E R G I Z E D W I R I N G W I L L C A U S E
S E V E R E I N J U R Y O R L O S S O F L I F E .
•
Turn off and lock-out/tag-out all power sources before proceeding to connect the power wiring to
the equipment.
•
Ensure that all power sources are turned off and isolated in accordance with established lock-out/
tag-out procedures before connecting the 3-phase power source wiring to the ASD input terminals
and connect the ASD output terminals to a motor of the correct voltage and type for the application
(refer to the NEC Article 300 – Wiring Methods and Article 310 – Conductors For General
Wiring). Size the branch circuit conductors in accordance with the NEC Table 310.16.
•
Ensure that the 3-phase input power is
NOT
connected to the output of the ASD. This will damage
the ASD and may cause injury to personnel.
•
If multiple conductors are used in parallel for the input or output power and it is necessary to use
separate conduits, each parallel set shall have its own conduit and not share its conduit with other
parallel sets (i.e., place U1, V1, W1, and a ground wire in one conduit and U2, V2, W2 and a
ground wire in another; refer to the NEC Article 300.20 and Article 310.4). National and local
electrical codes should be referenced if three or more power conductors are run in the same conduit
(refer to the NEC Article 310 adjustment factors).
Note:
National and local codes should be referenced when running more than three
conductors in the same conduit.
•
Ensure the correct phase sequence and the desired direction of motor rotation in the
Bypass
mode
(if applicable).
WARNING
DANGER
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...