174
HX7+ ASD Installation and Operation Manual
Brake Trouble Internal Timer
Program
Protection
Brake Fault Timer
This parameter is used in conjunction with the discrete input terminal setting
64
[
System Consistent Sequence
(BA: braking answer)] (see item
64
for further information on this feature).
After activating the discrete input terminal
System Consistent Sequence
(B:
braking release), the setting of this parameter defines a window of time in
which 1) a
Braking Answer
response must be received or 2) the brake must
release.
Should this timer setting expire before the
Braking Answer
is returned or the
brake releases, a
Brake Fault
is incurred. Otherwise, the brake releases and
normal motor operations resume.
Direct Access Number — F630
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Position Difference Limit
Program
Feedback Parameters
Feedback Settings
While operating in the
Position
Control
mode, this parameter sets the
maximum allowed difference between the commanded position and resulting
position as indicated by encoder pulses.
Direct Access Number — F631
Parameter Type —
Numerical
Factory Default —
16.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 6553
Release After Run Timer
Program
Protection
Brake Fault Timer
This parameter sets the time that the brake will hold after the
Run
command
criteria has been met.
Direct Access Number — F632
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Alarm Level
Program
Special Control
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm
activation criteria.
Direct Access Number — F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Earth Fault Alarm Time
Program
Special Control
Earth Fault
In the event that the
Earth Fault Alarm
activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the
Earth Fault Alarm
is
activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F641
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...