160
HX7+ ASD Installation and Operation Manual
Group #1 Speed Repeat Factor
Program
Pattern Run
Speeds
This parameter sets the number of times that the pattern defined in
Group #1
will be run.
Direct Access Number — F530
Parameter Type —
Numerical
Factory Default —
1
Changeable During Run —
No
Minimum — 1
Maximum — Infinite
Group #1 Speed #1
Program
Pattern Run
Speeds
Up to four groups of
Preset Speeds
may be setup and run from this screen. The
Preset Speed
numbers (1 – 15) may be entered into the
Speed #
field to be run
for the number of times entered into the
Repeat
field (0 – 254) or forever by
selecting
Infinite
. Running multiple
Preset Speeds
as a group is called a
Pattern Run
.
This parameter allows the user to run the
Preset Speeds
1 – 15 as a group and
is identified as
Group #1
.
Skip
may be selected to ignore a
Preset Speed
entry.
See
for further information on this setting.
Direct Access Number — F531
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
No
Group #1 Speed #2
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F532
Parameter Type —
Selection List
Factory Default —
2
Changeable During Run —
No
Group #1 Speed #3
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F533
Parameter Type —
Selection List
Factory Default —
3
Changeable During Run —
No
Group #1 Speed #4
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F534
Parameter Type —
Selection List
Factory Default —
4
Changeable During Run —
No
Group #1 Speed #5
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F535
Parameter Type —
Selection List
Factory Default —
5
Changeable During Run —
No
Group #1 Speed #6
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F536
Parameter Type —
Selection List
Factory Default —
6
Changeable During Run —
No
Group #1 Speed #7
Program
Pattern Run
Speeds
Same as
#1 Group Speed #1
(see
Direct Access Number — F537
Parameter Type —
Selection List
Factory Default —
7
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...