HX7+ ASD Installation and Operation Manual
29
Terminal Descriptions
Note:
The programmable terminal assignments may be accessed and changed from the
default settings as mapped on
or via the
Direct Access
method: Program
Direct Access
applicable parameter number
. See the section titled
Screen Menu Navigation on pg. 59
for the applicable
Direct Access
parameter
numbers. For further information on terminal assignments and default setting
changes, see the sections titled
Default Setting Changes on pg. 45
and
Note:
Cable/Terminal Specifications on pg. 231
for the ASD conductor
and terminal electrical specifications.
ST
— The default terminal assignment is
Standby
mode controller. As the default setting, this terminal
must be activated for normal system operation (system is in
Standby
when activated). The
ST
terminal
is activated by connecting
CC
to this terminal (Sink mode). If not connected to
CC
,
Off
is displayed on
the LCD screen. This input terminal may be programmed to any of the functions that are listed in
(see
RES
— The default terminal assignment is
Reset
. As the default setting, this terminal resets any active
alarms or faults. The
RES
terminal is activated by connecting
CC
to this terminal (Sink mode). A
momentary connection to
CC
resets the ASD and any fault indications from the display.
Reset
is
effective when faulted only. This input terminal may be programmed to any of the functions listed in
(see
). See the section titled
Alarms, Trips, and Troubleshooting on pg. 195
for a listing of the faults that do not respond to a reset.
F
— The default terminal assignment is
Forward
run. As the default setting, this terminal provides a
forward run command. The
F
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in
(see
).
R
— The default terminal assignment is
Reverse
run. As the default setting, this terminal provides a
reverse run command. The
R
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in
(see
S1
— The default terminal assignment is
Preset Speed 1
. As the default setting, this terminal provides
a
Preset Speed 1
run command. The
S1
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 1
. This input terminal may be programmed to any of the
(see
S2
— The default terminal assignment is
Preset Speed 2
. As the default setting, this terminal provides
a
Preset Speed 2
run command. The
S2
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 2
. This input terminal may be programmed to any of the
(see
S3
— The default terminal assignment is
Preset Speed 3
. As the default setting, this terminal provides
a
Preset Speed 3
run command. The
S3
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 3
. This input terminal may be programmed to any of the
(see
S4
— The default terminal assignment is
Emergency Off
. As the default setting, this terminal provides
an off command and may apply a brake if so configured (see
S4
terminal is activated by
connecting
CC
to this terminal (Sink mode). A connection to
CC
provides an
Emergency Off
command that terminates the ASD output. A
Reset
or restart is required to resume normal ASD
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...