background image

ALARM CONTROL UNIT 

 

CPX200NWB 

 

Installation and 

programming manual 

 

Version of the manual:   

 

 

v1.17 

Date of issue:   

 

 

 

2016.06.24 

Firmware version: 

 

 

 

2.4.13 

GPRS transmitter configurator version:   

1.3.60.3 

OSM server version: 

 

 

 

1.3.59.1 

 

Summary of Contents for CPX200NWB

Page 1: ...ONTROL UNIT CPX200NWB Installation and programming manual Version of the manual v1 17 Date of issue 2016 06 24 Firmware version 2 4 13 GPRS transmitter configurator version 1 3 60 3 OSM server version 1 3 59 1 ...

Page 2: ...ll not be deemed to be providing any warranties either express or implicit including but not limited to any implied warranties of merchantability or fitness for a particular purpose unless it is required by relevant law The manufacturer reserves the right to amend the present document or withdraw it any time without notice The manufacturer of the equipment promotes the sustainable development poli...

Page 3: ...SING DEVICES CONNECTED TO THE KEYPAD BUS 20 3 7 CONTROL PANEL LOCATION 21 3 8 WIRELESS DETECTORS INSTALLATION RECOMMENDATIONS 22 4 SERVICE MODE 23 4 1 ACTIVATION OF SERVICE MODE 24 4 2 EXIT FROM SERVICE MODE 24 4 3 INSTALLER MENU 24 4 3 1 INSTALLER CODE 24 4 3 2 POWER LOSS 25 4 3 3 RESET TO DEFAULT SETTINGS 25 4 3 4 SYSTEM OPTIONS 25 4 3 5 USERS REMOTE MANAGEMENT 26 4 3 6 ZONES CONFIGURATION 26 4 ...

Page 4: ...THORIZATION 72 6 4 5 ALARMS AND INPUTS INTERLOCKING STATES ARE NOT DISPLAYED 73 6 4 6 TEMPORARY KEYBOARD LOCK AFTER THREE ACCESS FAILURES 73 6 4 7 USE DURESS CODE 73 6 4 8 SHOW PARTITION ARMING MODE INSTEAD OF INPUTS INTERLOCKING STATES 73 6 5 USERS 73 6 6 MONITORING 74 6 6 1 EVENTS 75 6 6 2 ADDITIONAL DATA 76 6 7 RESTRICTIONS 77 6 7 1 SMS AND DATA CALLS CSD 77 6 7 2 REMOTE COMMANDS 80 6 8 SMS NOT...

Page 5: ...UTS 109 10 CHANGE HISTORY 118 LIST OF DRAWINGS AND DIAGRAMS DRAWING 1 DESCRIPTION OF PCB ELEMENTS 10 DRAWING 2 DESCRIPTION OF SCREW TERMINALS OF THE CONTROL UNIT 14 DRAWING 3 CONFIGURATION OF INPUT LINES 15 DRAWING 4 SAMPLE CONNECTION OF INTERNAL SIGNALLING DEVICE WITHOUT INDEPENDENT SOURCE OF POWER SUPPLY 16 DRAWING 5 SAMPLE CONNECTION OF EXTERNAL SIGNALLING DEVICE WITH INDEPENDENT SOURCE OF POWE...

Page 6: ...he central unit is equipped with 3 outputs and 16 zones with the possibility to be divided into 2 partitions Dedicated KP16 LED keypad was designed in a modern discreet style Portable size large comfortable buttons and simple installation contribute to indisputable advantage of our system The product was designed in accordance with the requirements of EN 50131 standards Grade 2 Environmental class...

Page 7: ... assign any number of zones to each of them KEYBOARD cooperation with LED keyboard KP16 ability to connect up to three keypads TRANSMISSION Transmission of signals through GPRS SMS module Encryption of data transfer using AES standard Communication with monitoring station using dedicated OSM 2007 server that ensures the reliability of data transfer thanks to a redundancy function Control of GSM GP...

Page 8: ...ad no sensors connected 120mA 1100mA 18VAC Average current consumption lack of external supply without keypad with keypad fully charged battery no sensors connected established connection with server 60mA 80mA Charging current measured with totalny discharged battrey max 350mA Charging voltage 13 8V Supported bartery type Lead acid 12V Low voltage event treshold 11V Voltage battery cut off level b...

Page 9: ... the keypad at the core diameter 0 5mm2 cannot exceed 200m 4 Install detectors and door and window reed relays Connect the installed elements with control unit For sample configuration of zones please refer to chapter 3 4 5 Install and connect signalling devices with the control unit For sample signalling devices connection diagrams please refer to chapter 3 5 6 Complete the remaining cable connec...

Page 10: ...mal GSM range The control unit is compatible with GSM antenna with male SMA connector This type of antenna should be install sellotape on nonmetalic surface plastic glass etc in vertical position foto attached below The hight placement position free of nearby objects will give You the best possible GSM signal Antenna shouldn t be placed in close range to metal objects especcialy wires Don t put an...

Page 11: ...ription of ERROR LED operation please refer to chapter 7 5 OK LED Green LED diode For the detailed description of OK LED operation please refer to chapter 7 6 CONF programming connector CONF IDC10 connector allows the control unit configuration using dedicated GD PROG programming device and any computer equipped with RS232 port 7 PROG Button for default settings restoration Pressing the button for...

Page 12: ...PX200NWB included two types of antennas internal and external dipole type 433MHz internal antenna Internal antenna can be used wherever required compact size and antenna provides appropriate coverage level detectors Ending of the internal antenna without isolation should be mounted in hot pole of the socket described as ANT correct pole is marked red on Drawing 1 Cold pole has been filled with pla...

Page 13: ...ernal antenna dipol type Antenna should be connected to GND and ANT connector regardings to the color on the endings of the wires Before screw the antenna remove plastic element from GND socket Correct install position for dipol antenna in the attached photo below 12 Wireless module The wireless module is used to receive signals from remote controls and wireless detectors ...

Page 14: ... MANUAL 14 118 3 3 DESCRIPTION OF SCREW TERMINALS OF THE CONTROL UNIT NOTE Any assembly and installation works shall be carried out with power supply off and battery disconnected Drawing 2 Description of screw terminals of the control unit ...

Page 15: ...ally closed NC or normally open NO as well as with assigned parameters EOL NO or EOL NC using 2 2kΩ resistors or with assigned double parameters DEOL NO or DEOL NC using 1 1kΩ resistors Both resistor types are included in the delivery of the control unit Various configurations of input lines are presented in the drawing 3 Drawing 3 Configuration of input lines ...

Page 16: ...LER MANUAL 16 118 3 5 SAMPLE CONNECTION OF SIGNALLING DEVICE 3 5 1 Internal signalling device without independent source of power supply Drawing 4 Sample connection of internal signalling device without independent source of power supply ...

Page 17: ...LARM CONTROL UNIT INSTALLER MANUAL 17 118 3 5 2 External signalling device with independent source of power supply Drawing 5 Sample connection of external signalling device with independent source of power supply ...

Page 18: ...and control unit operation After first pressing any button the keypad is backlit After a few second idle time backlight gets automatically dimmed In order to make codes easier to remember buttons are marked with the alphabet 2 ALARM LED red Flashing light means that alarms were present in the system alarm memory Constant light means that system is in alarm state Off system is operating correctly ...

Page 19: ...ng normal operation it means that the line it is assigned to was disrupted Flashing LED means the zone was interlocked After activating service functions LEDs display data 7 Screw terminals The connectors for connecting cables joining the keypad with the alarm control unit 8 Cable entry It is a place for entering the connection cables 9 Assembly holes The keypad was equipped with four round assemb...

Page 20: ...should choose the appropriate screws indywidually 5 Connect cables joining the keypad with the alarm control unit Keypad terminals marked KT KR KP KG shall be connected with KT KR KP KG terminals in the alarm control unit see drg 2 6 Assembly the rear part of the casing with the front one starting from the casing s top Make sure that the keypad is well assembled and sabotage switch is pressed in 3...

Page 21: ...etectors See drawings 7 and 8 Drawing 7 Control panel horizontal location Drawing 8 Control panel vertical location The radio waves are attenuated by walls and other obstacles Lowest attenuation have wallboards and wooden frame Medium attenuation have light concrete and brick walls Reinforced concrete and metal latticed plaster have the greatest attenuation The drawing 9 shows the signal loss thro...

Page 22: ...RS INSTALLATION RECOMMENDATIONS The wireless detectors should be located relative to the panel in such a way as to be on the same side of the control panel as the radio antenna and electronic components In this way you get the best radio coverage Additional installation tips describes the drawing 10 Drawing 10 Sensor placement ...

Page 23: ...16 may be changed by long press the buttons 0 6 The installer can change the option status as many times as they want When the desired status is set press to confirm or to exit without saving changes Decimal type DEC Service function that accepts decimal type arguments can also accept any length strings of decimal numbers not exceeding the maximum length pre defined for the function When a charact...

Page 24: ...e control unit s reset using configured parameters The device will exit test mode automatically after 5 minutes without pressing the buttons and system will restart 4 3 INSTALLER MENU After enter the service mode You get permision to configure alarm central By this commands You can get into some menu sections more information about procedures You will get in chapters bellow Instaler code change Po...

Page 25: ...ode You can press any time to exit without saving changes 4 3 4 System options That function allow to switch on and switch off additional options of the system The argument of the function is BIT type By pressing 1 2 3 4 5 and 6 keys you can switch on off proper option 3 beeps will confirm the successfully entered function Options Where Options number of option BIT type parameter 1 Enable faults m...

Page 26: ... support the duress code Upgrading the Firmware to version 2 1 0 or newer one has to make sure that there are no conflicts between existing users and their duress codes 8 Show partition arming mode instead of inputs interlocking states By default systerm will show violated and interlocked zones on diodes 1 8 Setting this option will tell the system to show partitoin armind mode on diodes 1 2 Zones...

Page 27: ...glary silent o 7 24h fire o 8 perimeter o 9 perimeter exit 2 delay in seconds for the circuit of selected delay response type DEC type parameter For other response types the parameter is irrelevant 3 operation mode DEC type parameter o 0 unused circuit o 1 NC mode o 2 NO mode o 3 EOL NC mode o 4 EOL NO mode o 5 DEOL NC mode o 6 DEOL NO mode o 7 Wireless mode 4 number of alarms after which the zone...

Page 28: ...vant output can be given subsequently or in a form of series of service functions that configure one output related parameter Codes of output configuration functions are defined as per the following pattern XX Y where XX determines the number of output from 01 to 03 entering number 00 will change the parameters for all outputs in the system Y number of parameter related to a given output 0 complex...

Page 29: ... output into bi stable operation mode b change of 3 output type into triggered by power failure c change of many parameters at the time for output 1 using complex function output 1 is to be set as alarm signalling with activation time 120 seconds 4 3 8 Partitions configuration Partition configuration can be configured similarly as zones and outputs using complex service functions after activation ...

Page 30: ...EC type parameter time of day written in the 24 hour notation in the form HHMM 7 auto arming option BIT type parameter o 1 auto arming activation deactivation 8 auto disarming time DEC type parameter time of day written in the 24 hour notation in the form HHMM 9 auto disarming option BIT type parameter o 1 auto disarming activation deactivation Notes Execution of complex function 3006 auto arming ...

Page 31: ... activation of which all the parameters related to the relevant zone can be given subsequently or in a form of series of service functions that configure one zone related parameter Codes of zone configuration functions are defined as per the following pattern XX Y Where XX determines the number of wireless zone from 01 to 16 entering number 00 will change the parameters for all zones in the system...

Page 32: ...ensor Note During the adding a new wireless detector function 2 the front cover of the detector should be removed It is recommended to add wireless sensors individually To prevent the accidental transmissions from other detectors only one detector cover should be removed during the procedure of adding a new detector Example a delete a wireless sensor no 10 b add a wireless sensor no 11 4 3 9 2 Sig...

Page 33: ... of which all the parameters related to the relevant remote control can be given subsequently or in a form of series of service functions that configure one remote control related parameter Codes of the remote control configuration functions are defined as per the following pattern XX Y Where XX determines the number of remote control Y number of parameter related to a given remote control 0 compl...

Page 34: ...d For normal and silent alarm can be sent a message to the monitoring station depending on the configuration of the control panel Example a delete a remote control no 1 b add a remote control no 1 4 3 10 2 Delete all remote controllers To remove all remote controllers from the system enter the following function After entering the function PROG LED is blinking the other LEDs are off Pressing key d...

Page 35: ...ssion first This can be achieved by typing in following code administrator code Next installer s access to text messages can be changed by pressing the key This will toggle led 1 When the led is active installer is granted the access when led is inactive installer is refused access to text messages Choice of installer s permissions can be accepted by pressing the button CPX200NWB can store up to 1...

Page 36: ... PARTITION2 default partitions names they can be changed with the SETNAME command X Y partition states possibile values 0 disarmed 1 armed GETARMED ERROR command rejected by the system Setting the name of partition Command syntax XXXX SETNAME PARTITION NR VALUE Command description Acquiring the information which partitions are armed disarmed XXXX user code NR number of the partition possibile valu...

Page 37: ...iption GETNAME PARTITION NR VALUE partition name GETNAME ERROR command rejected by the system Setting the phone number Command syntax XXXX SETTELNUM ID NUMBER Command description Setting the phone number for pointed index on the phone number list XXXX user code ID index of phone number on the list possible values 1 to 10 NUMBER phone number on which the texts will be send Example 1234 SETTELNUM 3 ...

Page 38: ...ck message description GETTELNUM ID NUMBER information about phone number GETTELNUM ERROR command rejected by the system Setting the content of text message Command syntax XXXX SETMESSAGE ID MESSAGE Command description Setting the content of text message under the pointed index XXXX user code ID index of text possible values 1 to 32 MESSAGE content of the text message Example 1234 SETMESSAGE 4 Rob...

Page 39: ...etting the content of text message under the pointed index XXXX user code ID index of text possible values 1 to 32 Example 1234 GETMESSAGE 30 Feedback message GETMESSAGE ID MESSAGE or GETMESSAGE ERROR Feedback message description GETMESSAGE ID MESSAGE information about the contents of text message GETMESSAGE ERROR command rejected by the system ...

Page 40: ...nes Each digit counting from the left represents an index of the phone number first digit for the first phone number second digit for the second number and so on 0 message will not be send to this number 1 message will be send to this number Example 1234 SETUSERSMS ARM1 1000000110 6 Means that when ARM1 event occurs partition 1 armed text message number 6 will be sent to phone numbers with indexes...

Page 41: ... number assigned to the specified event XXXX user code EVENT a short name of the event possible event names are listed at the end of this chapter Example 1234 GETUSERSMS ARM1 Feedback message GETUSERSMS EVENT TELNUM MSG_ID or GETUSERSMS EVENT ERROR Feedback message description GETUSERSMS EVENT TELNUM MSG_ID information about text message and phone number assinged to the event GETUSERSMS EVENT ERRO...

Page 42: ...f zones 1 16 ended INPUT1 TAMPER to INPUT16 TAMPER Sabotage of zones 1 16 INPUT1 TAMPEREND to INPUT16 TAMPEREND Sabotage of zones 1 16 ended INPUT1 LOCK to INPUT16 LOCK Bypass of zones 1 16 INPUT1 UNLOCK to INPUT16 UNLOCK Bypass of zones 1 16 ended OUTPUT1 ON to OUTPUT3 ON Zones 1 3 triggered OUTPUT1 OFF to OUTPUT3 OFF Zones 1 3 trigger ended OUTPUT1 TAMPER to OUTPUT3 TAMPER Fault of zones 1 3 OUT...

Page 43: ...P BEGIN Help alarm started KEYPAD SILENTALARM BEGIN Panic alarm started KEYPAD FIRE END Fire alarm ended JAMMING BEGIN GSM jamming JAMMING END GSM jamming ended DETECTOR1 LOST to DETECTOR16 LOST Detector 1 16 signal lost DETECTOR1 OK to DETECTOR16 OK Detector 1 16 signal restored DETECTOR1 PWR to DETECTOR16 PWR Detector 1 16 battery low DETECTOR1 PWROK to DETECTOR16 PWROK Detector 1 16 battery res...

Page 44: ...nserted before the configuration settings transmission is initiated In this case use either SIM cards with PIN code authorization deactivated or change the PIN code using a mobile phone before the card is inserted into the equipment 5 2 COMPUTER REQUIREMENTS The minimum requirements for PC computer on which the configuration wizard is to be installed are the following Hardware Processor Pentium II...

Page 45: ...ded settings you can use it for programming another equipment First indicate a directory where the file was saved then give the file name User can modify the received data In order to be effective the implemented changes must be sent to the equipment 5 3 1 3 File Save If you program many pieces of equipment in various configurations you do not need to remember each configuration You can save all s...

Page 46: ...connector of the alarm control unit The connection is executed through a dedicated programming cable using RS 232 serial port To program the equipment or perform other activities i e read the settings from the equipment change the firmware etc you have to define the connection parameters For the above purpose you shall use the above window available after activating File option from the Main Menu ...

Page 47: ... pl Enter the port on which analyser will listen to instructions e g 9000 Click Add button to confirm the setting The connection is saved and moved to the table From that moment the program will enable a remote connection with the equipment and allows reading and saving the parameters in the equipment s memory NOTE Such parameters as analyser s name analyser s address port refer to the settings of...

Page 48: ...system is installed with at least one GSM modem connected If the device is registered for the server serial number and SIM card number see OSM 2007 Manual you can use the connection via OSM Provided that no GPRS connection is established Programming attempt via GPRS connection see the above will end with a question whether you want to use a modem connected to the server If the answer is yes the pr...

Page 49: ... 3 and then use it for other devices You can use that function after you define a type and parameters of the connection E g for local connection the following window is displayed where Connection type of connection to the device Service code access code of the equipment For detailed description of connection configuration please refer to item 5 3 1 5 5 3 2 2 Operations Write The function is simila...

Page 50: ...guration with default values Upon confirmation the connection definition window will be displayed The operation is possible using local connection only After the operation is completed the equipment parameters will return to default factory settings 5 3 2 4 Operations Events history The function enables to read out the events lately recorded in the memory of the equipment Please refer to chapter 6...

Page 51: ... the equipment Switch the power off and disconnect the programming cable or switch the programming device into DEBUG mode Insert SIM card Re connect the power supply The equipment is ready for operation 5 4 2 Remote programming Remote programming of the equipment is possible in two cases User has a configuration wizard of GPRS transmitters and computer connected GSM modem User works based on the r...

Page 52: ...he server in Equipment tab it will be marked green Start the software and define the options of the equipment for description please refer to chapter 7 Select Send function The window will appear where you have to select the previously defined remote connection chapter 5 3 1 5 2 Copy the settings into the memory of the equipment Close the configuration wizard s window after you finish the data inp...

Page 53: ...ion mode Depending on user s preferences the equipment can operate in one of 4 modes to be selected from a drop list GPRS SMS GPRS transmission TCP IP protocol in standard and in case of problems with that connection automatic switch into SMS mode SMS Transmission only in SMS mode without the attempt of establishing a GPRS connection GPRS GPRS transmission TCP IP protocol in standard In case of an...

Page 54: ...e as often as in case of GPRS transmission is usually undesirable That parameter allows significant extension of interval between tests time in minutes or disabling that option 6 1 1 5 Telephone number of a server If to the server application e g OSM 2007 a GSM modem is connected here you have to enter its number SMS messages will be sent to this number in case the equipment encounters problems wi...

Page 55: ...mputer on which Communication server software is installed e g 89 123 115 8 The address can be given as a server s domain name e g modul gprs com In such a case at least one DNS server address is required 6 1 3 2 Server port It defines a port which was dedicated in the server for the receipt of data from the equipment 6 1 3 3 Interval between subsequent attempts The programmed equipment with SIM c...

Page 56: ...ment will retry to connect with a server in case the previous attempt was unsuccessful 6 1 4 4 Number of attempts of establishing connection with a server You can define how many times the equipment will try to connect with a secondary server In case of subsequent unsuccessful attempts after the defined number of attempts is executed the equipment will return to the procedure of connecting to prim...

Page 57: ...be changed via OSM 2007 Console In such case please send following Custom command SETPARAM 3 1 new_code where new_code should contain from 4 up to 7 digits 6 1 5 3 SIM Card PIN code Since the equipment uses GSM network for its operation it is necessary to obtain a SIM card from a mobile network operator You have to set a PIN code of a SIM card dedicated for operation in particular equipment before...

Page 58: ...he maximum transmission security the data transmitted are encrypted using AES The option can be used for both GPRS and SMS transmissions In case encrypted transmission was selected you can enter own data encryption key DEK 256 bits 0 9 and A F characters or use default setting ...

Page 59: ...nfiguration types are available NO NC EOL NO EOL NC DEOL NO DEOL NC Wireless NC type input must be closed for the whole time Line interruption causes its induction NO type input remains open It activates when closed EOL and DEOL with parameters or double parameters assigned differ in the number of resistors allowing to distinguish alarm from sabotage Electric diagrams for all configuration types w...

Page 60: ...ion of the zone event without the alarm In case of trigger when partition is armed it generates violation of the zone event and raises the alarm Interior delay the line can be used when keypad is not in the first partition which could be triggered during access to the keypad In case of the interior delay partition is triggered system checks if time for enter is counting If yes the line is treated ...

Page 61: ...ill be generated which allows to inform the monitoring station about the problem with the line This lock will last until disarming If the input is selected as the Alarm after time for exit then Interlocking after time for exit has priority the zone will be blocked and will not generate an alarm If the line is set to After time for exit and is violated or sabotaged after the time for exit then is a...

Page 62: ...me from the zone disruption was detected after which an alarm is generated 6 3 1 6 Alarm after time for exit Enabling this option causes the panel immediately generates an alarm when the zone was violated when the system is armed 6 3 1 7 Ignore during arming Zone can be violated during partition arming e g delay circuits shall be set to that option ...

Page 63: ...event the accidental transmissions from other detectors only one detector cover should be removed during the procedure of adding a new detector In order to add a wireless input click Add Device New window will appear where proper connection has to be chosen serial port number to which CPX200NWB is connected to and service code has be typed in In new window choose proper connection serial port numb...

Page 64: ...e waiting for a wirells signal to come User has to press for a while the tamper switch on the sensor CPX200NWB will detect the transmission and print sensor s type and ID To bind this sensor with the Alarm Control Unit press Add Device New sensor will appear in the previously selected Zone row ...

Page 65: ...CPX200NWB ALARM CONTROL UNIT INSTALLER MANUAL 65 118 Sensor preferences can be set now in the Inputs tab You can choose the same options as for wired zones excluding sensitivity ...

Page 66: ...return will be ignored 6 3 3 2 Entry Exit The parameter allows switching off the indication of time for entry exit displayed by KP16 keypad 6 3 3 3 Time for exit It is time for leaving the partition Assigned zones will be active monitored after the expiration of pre defined time counting from the time the arming zone was disrupted 6 3 3 4 Alarm time The parameter defines the time the alarm will be...

Page 67: ...or each input line is available Interlocking after time for exit option If this option is active in the case of arming with violated zone after time for exit will be generated event about blocked zone Zone blocking will continue until partition disarming see item 6 3 1 3 Interlocking When set to the same time arming and disarming the system will first be disarmed and then immediately armed If the ...

Page 68: ...Communication loss Output is activated when information transmission to server is not possible GSM jamming indicator Output is activated when jamming GSM Chirp The output is activated when arming 1 chirp or disarming 2 chirps The minimum duration of the chirp signal possible to set from the configurator is 40ms In the case of set time for exit chirp is generated after arming similarly in the case ...

Page 69: ...e changed only with remote command 6 3 5 Remote controllers Configurator allows adding and configuring remote controllers in the same way as it was done in the Wireless Inputs configuration In order to add a remote controler User has to select a row coressponding to desired remote controller and press the Add Device button New window will appear where necessary serial port configuration and servic...

Page 70: ...from Button 1 to Button 4 Remote controller can have less then 4 buttons in that case additional Button colums should be left with the None option selected NOTE The selected user number must be activated by the Administrator For this user number should be generated an access code Alarm function is triggering an alarm with audible signal Silent alarm function is triggering an alarm without audible ...

Page 71: ...function key support Events associated with emergency buttons will be transmitted to monitoring station only if they are enabled in the Monitoring tab see item 6 6 6 3 6 2 Outputs User can choose which outputs should be turned on in case of the emergency button activation pressing and holding a button for 3 seconds Each of the outpus has the reminder of it s function chosen in the Outputs tab ...

Page 72: ... Selecting this option turns off signaling a loss of communication with the server on KP16 keypad 6 4 3 Turn automatic override for failure off Selecting this option enables the system fault signal when arming 6 4 4 Access to alarm and fault memory requires authorization Selecting this option enables limitation to access to alarm memory and fault memory Checking alarm memory and fault memory will ...

Page 73: ...tress event Each user has his own duress code NOTE Firmware versions older than 2 1 0 do not support the duress code Upgrading the Firmware to version 2 or newer one has to make sure that there are no conflicts between existing users and their duress codes 6 4 8 Show partition arming mode instead of inputs interlocking states Show partition arming mode instead of inputs interlocking states By defa...

Page 74: ...t be selected in the writing options Users configuration changes can be made only via programming cable Users update is not possible remotely via GPRS 6 6 MONITORING That option allows determining which of available signals generated by the equipment will be transmitted to the monitoring station NOTE The Configuration change event refers to configuration change via SMS or via GPRS instructions onl...

Page 75: ...ss Clear button to remove all checked signals Press Reverse to reverse the check into the opposite ones 6 6 1 2 SMS ON OFF In these columns you can check which signals are to be reported to the monitoring station via SMS message when the equipment is not connected with server via GPRS connection You have the option to send information on both alarms change of input state from idle into active and ...

Page 76: ...vents to monitoring station via GPRS SMS The data may become valuable information about device s work conditions though it may increase amount of bytes sent through GSM network It is possible to define two separate sets of additional data kinds for test events sent periodically according to setting on Access tab and for other events Put a mark next to the name of data kind to turn on transmission ...

Page 77: ...nly Available options are Restrict all Means no possibility of communication Allow all Means that communication is allowed from any telephone number Allow selected Means that communication is allowed only from these listed telephone numbers You can define up to 5 telephone numbers When Allow selected box is selected you receive access to an edit box Enter the subsequent numbers in the box and clic...

Page 78: ...om these listed telephone numbers You can define up to 5 numbers When Allow selected box is checked you receive access to an edit box Enter the subsequent numbers in the box and click Add button to move the number to the table below To remove the number from the table place the cursor in a particular number line and click Remove Remove all option will clear all the numbers from the table NOTE Inco...

Page 79: ...s important mainly for economic reasons Check the Activate SMS restrictions check box to activate the access to information groups subject to restrictions SMS tests to server SMS events sent to server SMS events sent to the user Replies to commands Restrictions are defined by specifying two values Max number of SMS Defines a maximum number of SMS sent in a time unit please refer to Counter reset p...

Page 80: ...6 7 2 Remote commands 6 7 2 1 Users remote management enable Selecting this option allows you to remotely configure user accounts ...

Page 81: ...ify users about occurrence of certain events by text message Before sending the message may occur an additional attempt a voice call see item 6 8 4 Options In order to add user s number to the notification list one has to type in the number next to the number index Device can handle up to 10 phone numbers ...

Page 82: ...ge has to typed in the Messages tab These messages can be later assigned to specific events in the Events tab Before sending the message may occur an additional attempt a voice call see item 6 8 4 Options NOTE In text messages can be used only alphanumeric characters as well as and space ...

Page 83: ...the Message column select one of the messages defined before To assign a number to an event a corresponding column from Num 1 to Num 10 has to be checked From now on whenever this event occurs a text containing selected message will be send to the selected phone numbers Before sending the message may occur an additional attempt a voice call see item 6 8 4 Options ...

Page 84: ...o call the device sends an SMS message Sending a message to the first user the first defined phone number is followed by an attempt to call the next user and send a message And so on A voice call to a single user occurs no more than once every 15 minutes 6 8 4 3 Remove unsent SMS messages on partition disarming If option is enabled disarming the partition removes all waiting SMS except the SMS mes...

Page 85: ...CPX200NWB ALARM CONTROL UNIT INSTALLER MANUAL 85 118 ...

Page 86: ...hone number can be composed of an empty sequence which means it is applicable to any telephone number Rules are processed in accordance with a pre defined sequence from the beginning to the end i e the result of processing of a given rule does not influence the processing of the subsequent rules It also means that a given SMS message can be sent to a few telephone numbers or that the same SMS can ...

Page 87: ...eters defining the equipment s response after leaving GSM network You can define after what time from the moment the connection was lost the equipment shall initiate activities aiming at its restoration The time is selected in a Reset after box and is defined in minutes Then define what activity shall be initiated by the equipment Select by checking an appropriate box at the response description M...

Page 88: ...and is defined in minutes Then define what activity shall be initiated by the equipment Select by checking an appropriate box at the response description Modem reset Device reset In case the equipment lost the GPRS connection it shall wait for a defined period of time after the fact was ascertained and then it shall perform stipulated tasks 6 10 FIRMWARE The equipment has integrated bootloader tha...

Page 89: ...now the equipment will operate under the control of a new firmware NOTE The firmware update procedure shall be carried out with special care as improperly performed operation can prevent the correct operation of the equipment 6 11 DEVICE MONITORING The function Device Monitoring allows the on going monitoring of the control unit s condition In order to use that functionality connect the alarm cont...

Page 90: ...equipment The control unit has an event log memory where about 5 thousand technical events can be recorded You can review the events history via GPRS and RS232 connection In the second situation first you have to connect the equipment to a PC computer via GD PROG cable Then in the Event History box select an appropriate RS232 port or GPRS connection enter access code and click Read button After co...

Page 91: ...CPX200NWB ALARM CONTROL UNIT INSTALLER MANUAL 91 118 ...

Page 92: ...lashing green LED 1 8 blinks The operation mode of the equipment is indicated by green LED which goes on for 2 seconds after the range is indicated In case the LED does not go on for 2 seconds after the range is indicated it means SMS mode of equipment operation Range indication is interrupted during data transmission after which the GSM range is displayed 7 3 TRANSMISSION During data transmission...

Page 93: ...ootloader remains in the equipment and repeated equipment programming is possible Description LEDs OK green ERROR red STATUS yellow No software in the equipment Software update Decryption of firmware received 7 6 NO SIM CARD OR SIM CARD DAMAGED In case of any problems with SIM card the equipment indicates it with a red ERROR LED and green OK LED LED Indication OK green ERROR red 7 7 SYSTEM ERROR D...

Page 94: ...he control panel The battery capacity should be sufficient to operate the system without a power supply for 12 hours In the GPRS Transmitters Configurator see item 6 4 or in the installer menu see item 4 3 4 set the System Options enable option Show failures history with SYSTEM diode disable option Ignore ATS failure enable option Turn automatic prevention override for failure off enable option Ac...

Page 95: ...arms is available only after user code has been entered information about alarms memory is available only after user code has been entered information about failures is available only after user code has been entered information about failures memory is available only after user code has been entered arming requires authorization prior to arming the control panel checks circumstances that may prev...

Page 96: ...nt when the device will need to use it there is no need to restart the unit However there are parameters changes to which will be detected only in special circumstances for example the server address If it is changed when the device is online a restart is needed When CPX200NWB boots up it will connect to the newly configured address In order to delete a parameter the message has to contain the nam...

Page 97: ...TS only Description Sets the OSM server address with which the device exchanges data Server_address can be given in the domain format eg device mycompany com domain or IP address such as 213 216 102 98 9 1 1 5 PORT Format PORT port Limitations A number between 1 65535 can be changed by ATS only Description Sets the OSM server address with which the device exchanges data 9 1 1 6 SMS Format SMS phon...

Page 98: ... Do not send several commands in one SMS message or one frame since only one command will be executed and it will not necessarily be the first command in the list 9 1 2 1 DISC Format DISC Limitations Can be executed by ATS only Description Disconnects TCP connection with OSM server 9 1 2 2 KILL Format KILL Limitations Can be executed by ATS only Description Restarts the GSM modem in the device Thi...

Page 99: ...2 5 GETCFG Format GETCFG Limitations Returns max 160 characters can be executed by ATS only Description Gets the current basic configuration of the device The parameters are returned in the following order SERVER PORT _APN_UN_PW _DNS0 Where _ Space character asci 0x20 SERVER OSM server address PORT OSM server port APN APN name by means of which the GPRS session is compiled UN APN user name PW APN ...

Page 100: ...output 1 in bistable state OUT 3 1 10 switch on output 3 for 10 seconds 9 1 2 7 FLUSH Format FLUSH x Limitations x is equal to 0 or 1 possible to execution only by ATS Description For x 0 it clears the queue of outstanding events to be sent to the OSM server This results in the loss of outstanding events the device generates then an event indicating the fact For x 1 it clears the event log of the ...

Page 101: ...e bit 1 counting from 0 means the output 1 bit 2 the output 2 and bit 3 the output 3 If the output is enabled the bit is set Battery_voltage battery voltage in mV 12000 12V If the battery is not connected the readings may be incorrect and be around 9V 9000 voltage_AC AC voltage at the AC terminals of CPX200NWB downstream the transformer in mV 18000 18V blocked_zones means the current status of the...

Page 102: ...he user number name is the text user name which may be empty partitions is the bit vector specifying the partitions to which the user is authorized bit 0 corresponds to the partition 1 bit 1 to the partition 2 The user with id 0 is the administrator CPGETUSERS EPERMISIONS If the administrator password specified is incorrect CPGETUSERS ENOT_ALLOWED If the command is sent via open SMS or the configu...

Page 103: ...e the partitions to which the user is authorized bit 0 corresponds to the partition 1 bit 1 to the patition 2 The command returns CPGETUSERID EOK id partitions If the user with the specified code exists CPGETUSERID EPERMISIONS If the specified password is incorrect CPGETUSERID ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPGETUSERI...

Page 104: ...r of the user whose authorizations are changed the partitions is the bit vector with the partitions to which the user should have the authorization bit 0 corresponds to the partition 1 bit 1 to the partition 2 adminPassword is the system administrator password The command returns CPSETUSERPPARTITIONS EOK id partitions If the change of the partition assignment was successful CPSETUSERPARTITIONS ENO...

Page 105: ...e user s password Id is the user identifier whose password is changed the password is his new password and the adminPassword is the system administrator password The command returns CPSETUSERPASSWORD EOK id It the command is completed dministrato CPSETUSERPASSWORD ENOT_EXISTS id If the specified user does not exist CPSETUSERPASSWORD EPERMISIONS id If the administrator password specified is incorre...

Page 106: ...authorization bit 0 corresponds to the partition 1 bit 1 to the partition 2 password is the password of newly created user and adminPassword is the the system administrator password The command returns CPADDUSER EOK id partitions When a user is added CPADDUSER EALREADY_EXISTS id partitions If the specified user already exists CPADDUSER EID id partitions If the specified user ID is incorrect CPADDU...

Page 107: ...TS or administrator If the command is executed by ATS specify adminPassword Description Delete the user Id is the user number adminPassword is the system administrator password The command returns CPDELUSER EOK id If the user is deleted CPDELUSER ENOT_EXISTS id If the specified user does not exist CPDELUSER EPERMISIONS id If you can not delete a user because the administrator password is incorrect...

Page 108: ...m administrator The command is designed to give the ability to remotely restore the password by monitoring station employees if it is forgotten NewPassword is the new password of the main user The command returns CPSETADMINPASSWORD EOK CPSETADMINPASSWORD ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPSETADMINPASSWORD ELENGTH If the...

Page 109: ...sponding to the zone 1 bit 16 corresponds to the zone 16 otherAlarmHistory a bit vector indicating the additional alarm memory from the last arming Bit 1 counting from 0 corresponding to the tamper keypad 1 bit 2 corresponds to the tamper keypad 2 bit 3 corresponds to the tamper keypad 3 bit 7 corresponds to the alarm from remote controls zoneTampers is a bit vector indicating the zone tampering B...

Page 110: ...cating the communication failures between wireless detectors and control panel Bit 1 counting from 0 corresponds to the zone 1 bit 16 corresponds to the zone 16 zonesPowerFailures is a bit vector indicating detectors power failures in wireless detectors means low battery in wireless detectors Bit 1 counting from 0 corresponds to the zone 1 bit 16 corresponds to the zone 16 partitionsStayAway is a ...

Page 111: ...e failures of power supply outputs Bit 0 means the output KPOUT bit 1 means the output AUX1 bit 2 means the output AUX2 powerInFailures is a bit vector informing about the failures of power supply Bit 0 means the supply network failures bit 1 means the battery failure keypadCommFailures is a bit vector informing about the failures of communication with keypads Bit 0 means the keypad 1 keypadPowerF...

Page 112: ...ector is optional It means that partitions in the bit vector will be armed in stay mode It is not allowed to change arm mode of an already armed partition system will reject an attempt of arming in stay mode the partition that is armed in away mode It will also reject an attempt of arming in away mode a partition that is armed in stay mode It is also not possible to arm in stay mode the partition ...

Page 113: ...ual to zero has no sense since it does not change anything if the partitions is 0 the user s password is not checked and the status returned by the command is equal to EOK Password is the code of the user who performs disarming The specified partitions will be armed from the user s id to whome the code belongs The command returns CPUNSETPARTITIONS partitionList EOK If the command is executed parti...

Page 114: ...ants to block Bit 1 counting from 0 means the zone 1 Sending a command with the argument of zones equal to 0 has no sense since it does not change anything Password is the system administrator or user password who has authorizations to the partition containing the blocked zones The command returns CPZONESLOCK EOK zones If the command is executed CPZONESLOCK ENOT_ALLOWED If the command was sent via...

Page 115: ... bit vector indicating the zones which one wants to unblock Bit 1 counting from 0 means the zone 1 Sending the commands with the argument of zones equal to 0 has no sense since it does not change anything Password is the system dministrator or user password The command returns CPZONESUNLOCK EOK zones If the command is executed CPZONESUNLOCK ENOT_ALLOWED If the command was sent via open SMS CPZONES...

Page 116: ...d is the system administrator or user password Returns a list of zones assigned to the partition in the format CPPARTITIONSGETZONES P1Zones P2Zones Where P1Zones P2Zones are the bit vectors indicating which zones are assigned to the first and second partition respectively Bit 1 counting from 0 means the zone 1 CPPARTITIONSGETZONES EPERMISIONS If the specified password is incorrect CPPARTITIONSGETZ...

Page 117: ... system dministrator or user password Returns a list of outputs assigned to the partition in the format CPPARTITIONSGETOUTPUTS P1Outputs P2Outputs Where P1Outputs P2Outputs are the bit vectors indicating which outputs are assigned to the first and second partition respectively Bit 1 counting from 0 means the output 1 CPPARTITIONSGETOUTPUTS EPERMISIONS If the specified password is incorrect CPPARTI...

Page 118: ...Inputs Outputs tab description update Added Call before sending SMS option 29 10 2015 i1 9 2 2 0 Call before sending SMS option updated 09 11 2015 i1 10 2 3 1 Updated 24h tamper zone description function Reset to default setting description and information about stay away mode 16 12 2015 i1 11 2 3 6 Removed chapter Alarm control unit handling Changed order of chapters 08 01 2016 i1 12 2 3 7 Added ...