HX7+ ASD Installation and Operation Manual
Input Terminal 15 Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
#15
input terminal.
Note:
The
#15
input terminal may be used without the
ASD-Multicom
option board.
Without the
ASD-Multicom
option board the
#15
terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable terminal
#15
to 1 of the 68 possible
Direct Access Number — F125
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Input Terminal 16 Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
#16
input terminal.
Note:
The #
16
input terminal may be used without the
ASD-Multicom
option board.
Without the
ASD-Multicom
option board the
#16
terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable terminal
#16
to 1 of the 68 possible
Direct Access Number — F126
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
OUT1 Output Terminal Assignment
Program
Terminal Selection
Output Terminal
This parameter sets the functionality of the
OUT1
(
A
&
C
)
output terminals to
1 of the 62 possible functions that are listed in
The on and off delay times of the
OUT1
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F130
Parameter Type —
Selection List
Factory Default —
Low
Changeable During Run —
No
OUT2 Output Terminal Assignment
Program
Terminal Selection
Output Terminal
This parameter sets the functionality of the
OUT2
(
A
&
C
)
output terminals to
1 of the 62 possible functions that are listed in
The on and off delay times of the
OUT2
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F131
Parameter Type —
Selection List
Factory Default —
RCH (Acc/Dec
Complete)
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...