![background image](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329047.webp)
2-4
Section
Connecting External I/O
34
The input section has both N.O. and N.C. inputs. Either can be used depending
on the axis parameter settings. For details regarding axis parameters, refer to
4-3 Axis Parameters Area
.
Name
Connection type
External interrupt input signal
N.O.
Emergency stop input signal
N.C.
Origin proximity input signal
N.C. or N.O.
CW limit input signal
N.C. or N.O.
CCW limit input signal
N.C. or N.O.
C200HW-NC113/213/413 Position Control Unit
24-VDC
power
supply
External
interrupt
input signal
Emergency
stop input
signal
Origin
proximity
input signal
CW limit
input signal
CCW limit
input signal
680
Ω
4.7 k
Ω
(1/2W)
680
Ω
680
Ω
680
Ω
680
Ω
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
Switch (N.O. contact)
Switch (N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)