![Omron C200HW Operation Manual Download Page 158](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329158.webp)
7-6
Section
Sample Program
147
7-6-3 Sample Program
For details on the operating data area, refer to
4-5 Operating Data Area
.
Data Configuration and Operating Data Area Set by the Program
Name
Configuration
DM
Contents
Position
x10
6
x10
5
x10
4
x10
3
x10
2
x10
1
x10
0
15
00
I+7
15
00
I+6
I+7
I+6
Sign
0: Plus
1: Minus
Set range is from –9999999 t9999999
0506
0507
5000
0013
Speed
I+8
x10
2
x10
1
x10
0
15 14 13 12
00
x10
3
Factor: 00: x 1, 01: x 10, 10: x 100, 11: x1,000
(Unit: pps)
0508
5500
Acceleration/
deceleration time
number
15
00
07
08
Acceleration time: 0 through 9
Deceleration time: 0 through 9
If “0” is set, the acceleration/deceleration times set in the
parameter data area (m+15 through m+18) will be used.
If “1” through “9” are set, acceleration/deceleration time from
No. 1 through No. 9 will be used.
0510
0000
Program Example
Start switch
Work bit
Sets position (leftmost).
Sets position (rightmost).
Sets speed.
Sets deceleration time
number.
RELATIVE MOVEMENT
Summary of Contents for C200HW
Page 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Page 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...