![Omron C200HW Operation Manual Download Page 19](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329019.webp)
1-2
Section
System Configuration
6
3. To remove the Unit. use an implement such as a screwdriver to press down
on the lock lever and then carefully lift the Unit out.
Lock lever
Note
When installing Units on a Rack, leave adequate space for mounting and remov-
ing the Units as shown in the following diagram.
Backplane
20 mm min.
20 mm min.
Flathead screwdriver
Precautions When Handling the Unit
•
Before installing or disconnecting the Unit or connecting cable, be sure to first
turn off both the Programmable Controller and the power supply.
•
To minimize any influence from noise, place I/O wiring, high-voltage lines, and
power lines in separate ducts.
•
Wire clippings tend to get scattered around during wiring, so leave the label in
place on top of the Unit to prevent any clippings from getting inside the Unit.
Once the wiring has been completed, be sure to remove the label to provide
ventilation.
Remove the label after
completing the wiring.
Summary of Contents for C200HW
Page 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Page 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...