5-1
Section
Transferring and Saving Data
97
3. There is a limit on the number of times you can read something using the
flash memory. Set this so that up to 100,000 data saving operations can be
performed.
Position Control Unit
Internal
memory
Flash
memory
Saving
Transferring
Parameter
data
At power
up or
restart
Positioning
All the following data used by the Position Control Unit can be read, written, and
saved to the flash memory.
The following types of data can be saved together in the flash memory.
•
Axis parameters (see note)
•
Positioning sequences
•
Speeds
•
Positions
•
Acceleration times
•
Deceleration times
•
Dwell times
•
Zones
Note
When the power is turned on or when the Unit is restarted, a choice is available
by using Specify Parameters in the DM area common parameters (refer to
4-2
Common Parameter Area
) between sending the axis parameters automatically
from the DM area to the Position Control Unit or using the axis parameters saved
in the Position Control Unit.
At power on
or restart
When parameter
designation = 01
(m+2)
Position Control Unit
Internal
memory
Flash
memory
Axis
param-
eters
Axis
param-
eters
When power is turned on or upon restarting
When parameter designation = 00
(m+2)
Data that Can be Saved
and/or Transferred
Summary of Contents for C200HW
Page 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Page 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...