![Omron C200HW Operation Manual Download Page 157](http://html1.mh-extra.com/html/omron/c200hw/c200hw_operation-manual_742329157.webp)
7-6
Section
Sample Program
146
7-6
Sample Program
This section provides a sample program for operating the axes. The Position
Control Unit used is a C200HW-NC113.
The factory settings in the PCU are used for the axis parameters. If the values
have been modified by data transfer, for example, the results achieved will vary
from those given below.
7-6-1 Details of Operation
The X axis is moved by relative movement at a speed of 15,000 pps to the posi-
tion at 135,000 pulses. The speed is not modified by override.
3 ms
3 ms
Speed
Position 135,000 pulses
Acceleration time 100 ms
Deceleration time 100 ms
Time
The values set for the acceleration and deceleration times and the actual accel-
eration and deceleration times are related to the values set for the actual target
speeds and maximum speeds for the axis parameter area. For details, refer to
Appendix B Estimating Times and Pulses for Acceleration/Deceleration
.
7-6-2 Setting Conditions and Details
The following table shows details of settings and conditions.
Item
Details
Unit number of Position Control Unit
Set to Unit #3.
Common parameter area: DM 1300 through DM 1302.
Operating memory area: Words 130 through 134.
The above areas are allocated automatically by setting the unit number.
Designation of operating data area
0
DM 1300
0
0
D
0
DM 1301
5
0
0
DM 0500
Unit mounting position and parameter
designation
0
DM 1302
0
0
0
Mount on the CPU Rack.
Use the Position Control Unit’s
existing parameters.
Summary of Contents for C200HW
Page 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Page 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...