2-2
Section
Components
22
LED Indicators
Name
Color
Status
Explanation
RUN
Green
Lit
Lit during normal operation.
Not lit
Hardware error, or PC notified of PCU error.
ERR
Red
Lit / flashing
An error has occurred.
Not lit
No error has occurred.
SENS
Red
Lit
Either a CW/CCW limit signal or an emergency stop input signal is being input. At
this time the LED indicator for the relevant axis (X to U) will flash.
Flashing
Either a parameter loss, a data loss, or an operating data area designation error
has occurred.
Not lit
None of the above has occurred.
DATA
Red
Flashing
The check of all data (parameters, positions, etc.) following power up shows that
data is lost or corrupted.
Lit
Data is incorrect (e.g., the parameters or positions transferred are out of the
permissible range). At this time the LED indicator for the relevant axis (X to U)
will flash.
DATA
Red
Not lit
None of the above has occurred.
X
Orange
Lit
Pulses are being output to the X axis (either forward or reverse).
g
Flashing
An error has occurred, such as incorrect cable type for the X axis or faulty data.
Not lit
None of the above has occurred.
Y
Orange
Lit
Pulses are being output to the Y axis (either forward or reverse).
g
Flashing
An error has occurred, such as incorrect cable type for the Y axis or faulty data.
Not lit
None of the above has occurred.
Z
Orange
Lit
Pulses are being output to the Z axis (either forward or reverse).
g
Flashing
An error has occurred, such as incorrect cable type for the Z axis or faulty data.
Not lit
None of the above has occurred.
U
Orange
Lit
Pulses are being output to the U axis (either forward or reverse).
g
Flashing
An error has occurred, such as incorrect cable type for the U axis or faulty data.
Not lit
None of the above has occurred.
Note
For details regarding errors, refer to
Section 11 Troubleshooting
.
•
For the C200HW-NC213, this applies only to the X axis; for the C200HW-
NC213, it applies only to the X and Y axes.
•
When not all of the axes are used for the C200HW-NC213 or C200HW-
NC413, either connect the CW/CCW limit inputs for the unused axes to the
input power supply and turn them ON or set the contact logic to N.O. Connect
the emergency stop to the input common and turn it ON. If it is not connected,
the ERR indicator will light. Operation will be normal, however, for all axes that
are used.
This switch sets the unit number (i.e., the machine number) for the PCU.
The permissible range of unit number settings depends on the type of Program-
mable Controller and the PCU model, as shown in the following table.
PC type
PCU model
Setting range
C200HX/HG-CPU3
j
/4
j
d ll C200HE/HS/H
d l
NC113/NC213
0 to 9
j j
and all C200HE/HS/H models
NC413
0 to 8
C200HX/HG-CPU5
j
/6
j
NC113/NC213
0 to 9, A to F
j j
NC413
0 to 8, A to E
Unit Number Setting
Switch
Summary of Contents for C200HW
Page 1: ...Cat No W334 E1 04 Position Control Units SYSMAC C200HW NC113 NC213 NC413 ...
Page 2: ...C200HW NC113 NC213 NC413 Position Control Units Operation Manual Revised July 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 285: ...Cat No W334 E1 04 C200HW NC113 NC213 NC413 Position Control Units OPERATION MANUAL ...