Item
Data
Remarks
Battery set
power-off
parameters
Battery set power-off permission
status: permit
You can change the configuration by
running the
power charge
command
according to the actual requirements.
Battery set power-off voltage: 43
V
High-
temperature
power-off
parameters of
the battery
Battery high-temperature
power-off permission status:
forbid
You can change the configuration by
running the
power charge
command
according to the actual requirements.
Temperature for battery high-
temperature power-off: 53°C
Rectifier unit
parameter
Number of rectifier units: 2
The EPS30-4815AF supports up to two
rectifier units.
Environment
monitoring
parameters
Upper alarm threshold of the
temperature: 68°C
You can change the configuration by
running the
power environment
command according to the actual
requirements.
Lower alarm threshold of the
temperature: -5°C
Upper measurement threshold of
the temperature: 80°C
Lower measurement threshold of
the temperature: -20°C
Upper alarm threshold of the
humidity: 80% RH
Lower alarm threshold of the
humidity: 10% RH
Upper measurement threshold of
the humidity: 100% RH
Lower measurement threshold of
the humidity: 0% RH
External
extended
digital
parameter of
the power
Extended digital parameter ID: 1 -
Valid level of extended digital
parameter 1: low level
When the low level represents the valid
level, the device does not report an
alarm in the case of low level.
Name of extended digital
parameter 1: Fan
It is a user-defined digital parameter and
is set according to the actual
requirements. The monitoring digital
parameter of the fan status sensor is set
to monitor the fan status.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
142