Monitoring Parameter on Host
Device Port
Analog 2
N/A
Analog 3
N/A
Wiring
JTP1 (MDF)
Door0
JTM1 (door status)
Digital 2
JTD1
Digital 3
JTD2
Digital 4
JTD3
Digital 5
JTD4
Digital 6
JTD5
Digital 7
JTD6
Smoke
JTD7 (smoke)
Water_Alarm
JTS1 (water)
NOTE
Before adding a user-defined analog or digital monitoring parameter, make sure that the port corresponding
to this analog or digital monitoring parameter is properly connected with an environment monitoring cable.
Procedure
Step 1
Add an EMU.
Run the
emu add
command to add an EMU to monitor the environment parameters of the device
so that the device runs in a stable environment.
The EMU ID is 3, the type is ESCM (MiniESC on the CLI), the subnode ID is 8, and the serial
port type isRS485.
Step 2
Configure the analog parameters.
Run the
esc analog
command to configure the upper/lower alarm thresholds and measurement
thresholds, thus supporting the real-time monitoring of the device through the analog parameters.
Step 3
Configure the digital parameters.
Run the
esc digital
command to configure the valid level, name, and alarm ID of the digital
parameters.
Step 4
Query the environment information about the ESCM.
Run the
display esc environment info
command to query the environment information about
the ESCM.
Step 5
Save the data.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
135