Item
Data
Remarks
Analog parameter ID: 2
The user-defined humidity monitoring analog
parameter is added to monitor the ambient
humidity of the device.
For values and details of this parameter, see the
esc analog
command.
Upper alarm threshold of
analog parameter 2: 75%
RH
When the ambient humidity of the device is
higher than 75% RH, the device reports an alarm.
Lower alarm threshold of
analog parameter 2: 5%
RH
When the ambient humidity of the device is
lower than 5% RH, the device reports an alarm.
Name of analog parameter
2: humidity
-
Alarm ID of analog
parameter 2: 2
The user-defined humidity alarm of the system
is used.
Unit of analog parameter
2: % RH
-
Sensor type of analog
parameter 2: voltage type
-
Digital
parameters
Digital parameter ID: 1
This parameter is invariably allocated by the
system, and is used to monitor the door status of
the telecommunications room. You cannot
modify any parameter of this digital parameter,
except the valid level.
Valid level of digital
parameter 1: high level
When the high level represents the valid level,
the device does not report an alarm in the case of
high level.
Digital parameter ID: 2
-
Valid level of digital
parameter 2: low level
When the low level represents the valid level, the
device does not report an alarm in the case of low
level.
Name of digital parameter
2: Fan
It is a user-defined digital parameter and is set
according to the actual requirements. The
monitoring digital parameter of the fan unit is set
here to monitor the fan unit.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.