SJ700
2
Inverter
Appendix C
C–11
C019
Terminal [FW] active state
00
00
00
C021
Terminal [11] function
01
01
01
C022
Terminal [12] function
00
00
00
C023
Terminal [13] function
03
03
03
C024
Terminal [14] function
07
07
07
C025
Terminal [15] function
08
08
08
C026
Alarm relay terminal function
05
05
05
C027
[FM] signal selection
00
00
00
C028
[AM] signal selection
00
00
00
C029
[AMI] signal selection
00
00
00
C030
Digital current monitor reference value
Rated current x 1.0
C031
Terminal [11] active state
00
00
00
C032
Terminal [12] active state
00
00
00
C033
Terminal [13] active state
00
00
00
C034
Terminal [14] active state
00
00
00
C035
Terminal [15] active state
00
00
00
C036
Alarm relay active state
01
01
01
C038
Low current indication output mode select
01
01
01
C039
Low current indication detection level
Rated current x 1.0
C040
Overload signal output mode
01
01
01
C041
Overload level setting
Rated current for each inverter
C042
Frequency arrival setting for accel.
0.00
0.00
0.00
C043
Arrival frequency setting for decel.
0.00
0.00
0.00
C044
PID deviation level setting
3.0
3.0
3.0
C045
Frequency arrival setting for acceleration (2)
0.00
0.00
0.00
C046
Frequency arrival setting for deceleration (2)
0.00
0.00
0.00
C052
Maximum PID feedback (PV) data
0.00
0.00
0.00
C053
Minimum PID feedback (PV) data
100.0
100.0
100.0
C055
Over-torque (forward-driving) level setting
100.
100.
100.
C056
Over-torque (reverse regenerating) level setting
100.
100.
100.
C057
Over-torque (reverse driving) level setting
100.
100.
100.
C058
Over-torque (forward regenerating) level setting
100.
100.
100.
C061
Electronic thermal warning level setting
80.
80.
80.
C062
Alarm code output
00
00
00
C063
Zero speed detection level
0.00
0.00
0.00
C064
Heatsink overheat warning level
120
120
120
“C” Group Parameters
Default Setting
User
Setting
Func.
Code
Name
FEF2, FE2
(Europe)
FU2, FU2
(U.S.A.)
FF2, F2
(Japan)