SJ700
2
Inverter
Getti
n
g Star
ted
1–7
Tables for 400V
class inverters
Note that
“General Specifications” on page 1–10
covers all SJ700
2
inverters, followed by
footnotes for all specifications tables. The 400V models from –007 to –220HFU2
(7.5 to 30 HP) include internal dynamic braking units (see
“Dynamic Braking” on page 5–6
).
Item
200V Class Specifications, continued
SJ700
2
, 200V models, U.S. version
300LFU2
370LFU2
450LFU2
550LFU2
Applicable motor size *2
HP
40
50
60
75
kW
30
37
45
55
Rated capacity, kVA, 200V / 240V
41.9 / 50.2
50.2 / 60.2
63.0 / 75.6
76.2 / 91.4
Rated input voltage
3-phase: 200 to 240V +10/-15%, 50/60 Hz ±5%
Rated input current (A)
133
160
200
242
Rated output voltage *3
3-phase (3-wire) 200 to 240V (corresponding to input voltage)
Rated output current (A)
121
145
182
220
Overload capacity, output current (A)
150% for 60 sec., 200% for 3 sec.
Efficiency at 100% rated output, %
95.0
95.1
95.1
95.1
Watt loss,
approximate (W)
at 70% output
1100
1345
1625
1975
at 100% output
1550
1900
2300
2800
Dynamic braking
approx. % torque,
short time stop *7
w/o braking unit
10
10
10
10
with braking unit
55–110%
45–90%
35–75%
30–60%
DC braking
Variable operating frequency, time, and braking force
Electrical filtering
Built-in EMC filter and built-in zero-phase reactor
Weight
kg / lb
22 / 48.4
30 / 66
30 / 66
43 / 94.6
Item
400V Class Specifications
SJ700
2
inverters,
400V models
U.S. version
007HFUF2
015HFUF2
022HFUF2
040HFUF2
055HFUF2
European ver.
007HFEF2
015HFEF2
022HFEF2
040HFEF2
055HFEF2
Applicable motor size *2
HP
1
2
3
5
7.5
kW
0.75
1.5
2.2
4
5.5
Rated capacity, kVA, 400 / 480V
1.7 / 2.0
2.5 / 3.1
3.6 / 4.3
5.7 / 6.8
9.7 / 11.6
Rated input voltage
3-phase (3-wire) 380 to 480V +10/-15%, 50/60 Hz ±5%
Rated input current (A)
2.8
4.2
5.8
9.9
13
Rated output voltage *3
3-phase (3-wire): 380 to 480V (corresponding to input voltage)
Rated output current (A)
2.5
3.8
5.3
9.0
14
Overload capacity, output current (A)
150% for 60 sec., 200% for 3 sec.
Efficiency at 100% rated output, %
89.5
92.3
93.2
94.0
94.4
Watt loss,
approximate (W)
at 70% output
76
102
127
179
242
at 100% output
88
125
160
235
325
Dynamic braking
approx. % torque,
short time stop *7
internal chopper
20
20
20
20
20
with external res.
>150
>150
>150
>150
130
Min. external braking resistance
Ω
100
100
100
70
70
DC braking
Variable operating frequency, time, and braking force
Electrical filtering
Built-in EMC filter and built-in zero-phase reactor
Weight
kg / lb
3.5 / 7.7
3.5 / 7.7
3.5 / 7.7
3.5 / 7.7
6 / 13.2