SJ700
2
Inverter
Appendix B
B–33
ModBus Data Listing
ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The table
legend is given below.
•
Coil Number -
The network register address offset for the coil, in hex and decimal. Actual
network address is 30001 + offset. The coil data is a single bit (binary) value.
•
Name -
The functional name of the coil
•
R/W -
The read-only (R) or read-write (R/W) access permitted to the inverter data
•
Description -
The meaning of each of the states of the coils
List of Coil Numbers
Coil number
Name
R/W
Description
hex
dec.
0000h
00000
(Reserved)
—
—
0001h
00001
Operation command
R/W
0 ... Stop
1 ... Run (enabled when A003=03)
0002h
00002
Rotation direction command
R/W
0 ... REV
1 ... FW (enabled when A003=03)
0003h
00003
External trip (EXT)
R/W
0 ... No trip event
1 ... Trip occurred
0004h
00004
Trip reset (RS)
R/W
0 ... No reset condition
1 ... Reset
0005h
00005
(Reserved)
—
—
0006h
00006
(Reserved)
—
—
0007h
00007
Intelligent input terminal [1]
R/W
0 ... OFF *1
1 ... ON
0008h
00008
Intelligent input terminal [2]
R/W
0009h
00009
Intelligent input terminal 3]
R/W
000Ah
00010
Intelligent input terminal [4]
R/W
000Bh
00011
Intelligent input terminal [5]
R/W
000Ch
00012
Intelligent input terminal [6]
R/W
000Dh
00013
Intelligent input terminal [7]
R/W
000Eh
00014
Intelligent input terminal [8]
R/W
000Fh
00015
Run/Stop status
R
0 ... Stop (corresponds to D003 monitor)
1 ... Run
0010h
00016
FW/REV status
R
0 ... FW
1 ... RV
0011h
00017
Inverter ready
R
0 ... Not ready
1 ... Ready
0012h
00018
(Reserved)
R
—
0013h
00019
RUN (running)
R
0 ... OFF
1 ... ON
0014h
00020
FA2 - Frequency Arrival
(constant-speed reached)
R
0015h
00021
FA2 - Frequancy Arrival (above
set frequency)
R
0016h
00022
OL - Overload signal
R
0017h
00023
OD - PID deviation signal
R