Comparator
Signals
The window comparator function outputs turn ON when You can also monitor each analog
input by comparing it to a threshold value. This feature allows the inverter to detect discon-
nected signal wiring, loss of power at a signal transmitter, etc. When the input is below the set
threshold value, the inverter substitutes the threshold value for the input. The related parameters
are given in the following tables.
The following signal diagram shows the window comparator output generated from input
signals and comparator settings listed along the Y axis.
Opt. Code
and
Symbol
54=[WCO]
55=[WCOI]
56=[WCO2]
Valid for
Ouputs
[11 to [15],
[ALx]
Required
Settings
none
Default
terminal
Requires
config.
Opt.
Code
Symbol
Function Name
54
WCO
[O] terminal window comparator
55
WCOI
[OI] terminal window comparator
54
WCO2
[O2] terminal window comparator
Code
Function
Range
Description
B060
[O] input maximum limit level of
window comparator
0. to 100. (%)
Lower limit = B061 + B062 x 2
B061
[O] input minimum limit level of
window comparator
0. to 100. (%)
Lower limit = B060 – B062 x 2
B062
[O] input hysteresis width of
window comparator
0. to 10. (%)
Lower limit = B061 – B062 x 2
B063
[OI] input maximum limit level
of window comparator
0. to 100. (%)
Lower limit = B064 + B066 x 2
B064
[OI] input minimum limit level of
window comparator
0. to 100. (%)
Lower limit = B063 – B066 x 2
B065
[OI] input hysteresis width of
window comparator
0. to 10. (%)
Lower limit = B063 – B064 x 2
B066
[O2] input maximum limit level
of window comparator
–100. to 100. (%) Lower limit = B067 + B068 x 2
B067
[O2] input minimum limit level
of window comparator
–100. to 100. (%) Lower limit = B066 – B068 x 2
B068
[O2] input hysteresis width of
window comparator
0. to 10. (%)
Lower limit = B066 – B067 x 2
[O], [OI], or [O2]
t
0
Hysteresis region
t
B062
B065
B068
[WCO], [WCOI], or [WCO2]
B060
B063
B066
B061
B064
B067
Hysteresis region