SJ700
2
Inverter
Appendix B
B–53
B003
— Retry wait time before
motor restart
R/W
Time delay after a trip condition
goes away before the inverter
restarts the motor
1303h
04867
3 to 1000
0.1 sec.
B004
— Instantaneous power
failure / under-voltage trip
alarm enable
R/W
00 .Disable
01 .Enable
02 .Disable during stop and
ramp to stop
1304h
04868
0, 1, 2
—
B005
— Number of restarts on
power failure / under-
voltage trip events
R/W
00 .Restart 16 times
01 .Always restart
1305h
04869
0, 1
—
B006
— Phase loss detection enable
R/W
00 .Disable
01 .Enable
1306h
04870
0, 1
—
B007
H Restart frequency thresh-
old
R/W
When the frequency of the motor
is less than this value, the
inverter will restart at 0 Hz
1307h
04871
0 to 40000
0.01 Hz
B007
L
R/W
1308h
04872
B008
— Retry after trip select
R/W
00 .Always retry after trip
01 .Start with 0 Hz
02 .Start with frequency
matching
03 .Retry after deceleration
and stop with matching
frequency
04 .Start with active
matching frequency
1309h
04873
0 to 4
—
B009
— Retry after undervoltage
select
R/W
00 .Restart 16 times
01 .Unlimited
130Ah
04874
0, 1
—
B010
— Retry count select after
overvoltage or overcurrent
R/W
1 to 3 (times)
130Bh
04875
1 to 3
times
B011
— Retry wait time after trip
R/W
0.3 to 100.0 (seconds)
130Ch
04876
3 to 1000
0.1 sec.
B012
— Electronic thermal setting
(calculated within the
inverter from current
output)
R/W
Range is 0.2 * rated current to
1.2 * rated current
130Dh
04877
200 to
1000
0.1 %
B212
— Electronic thermal setting
(calculated within the
inverter from current
output), 2nd motor
R/W
Range is 0.2 * rated current to
1.2 * rated current
230Ch
08972
200 to
1000
0.1 %
B312
— Electronic thermal setting
(calculated within the
inverter from current
output), 3rd motor
R/W
Range is 0.2 * rated current to
1.2 * rated current
330Ch
13068
200 to
1000
0.1 %
B013
— Electronic thermal charac-
teristic
R/W
00 .Reduced torque
01 .Constant torque
02 .Free-setting
130Eh
04878
0, 1, 2
—
—
(Reserved)
—
130Fh
04879
—
—
B213
— Electronic thermal charac-
teristic, 2nd motor
R/W
00 .Reduced torque
01 .Constant torque
02 .Free-setting
230Dh
08973
0, 1, 2
—
—
(Reserved)
—
—
230Eh
to
2501h
08974
to
09493
—
—
Holding Registers, “B” Group Fine Tuning Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.