ASCII Mode Communications
Append
ix
B
B–10
The data in the receive frame contains 8-byte values for 13 items, listed in the table below:
The eight bytes for intelligent input or intelligent output data have a bit set in the data field for
each I/O point that is ON, according to the following table:
No.
Monitor Item
Units
Multiplier
Data
Size
Notes
1
Output frequency
Hz
100
8 bytes
Dec. ASCII code
2
Output current
A
10
8 bytes
Dec. ASCII code
3
Direction of rotation
—
—
8 bytes
0 = Stop
1 = FWD
2 = REV
4
PID feedback monitor
%
100
8 bytes
Dec. ASCII code
5
Intelligent input monitor
—
—
8 bytes
Dec. ASCII code
6
Intelligent output monitor
—
—
8 bytes
Dec. ASCII code
7
Frequency converting monitor
—
100
8 bytes
Dec. ASCII code
8
Output torque monitor
%
1
8 bytes
Dec. ASCII code
9
Output voltage monitor
V
10
8 bytes
Dec. ASCII code
10
Electric power monitor
kW
10
8 bytes
Dec. ASCII code
11
Reserved
—
—
8 bytes
= 00000000
12
Run Mode time monitor
hours
1
8 bytes
Dec. ASCII code
13
Power ON time monitor
hours
1
8 bytes
Dec. ASCII code
Terminal
Monitor Item
Data
[1]
Input 1
00000001
[2]
Input 2
00000002
[3]
Input 3
00000004
[4]
Input 4
00000008
[5]
Input 5
00000010
[6]
Input 6
00000020
[7]
Input 7
00000040
[8]
Input 8
00000080
[FW]
Forward input
00000100
[11]
Output 1
00000001
[12]
Output 2
00000002
[13]
Output 3
00000003
[14]
Output 4
00000008
[15]
Output 5
00000010
[AL]
Alarm relay
00000020