“A” Group: Standard Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–28
Target Frequency
Operation
Analog Input Calculate Function –
The inverter can mathematically combine two input
sources into one value. The Calculate function can either add, subtract, or multiply the two
selected sources. This provides the flexibility needed by various applications.You can use the
result for the output frequency setting (use A001=10) or for the PID Process Variable (PV)
input (use A075=03).
A105
[OI]–[L] input start frequency enable
OI-EXS
00
Use A101 start value
01
01
01
✘ ✔
0Hz
0 1
Use 0Hz
A111
[O2]–[L] input active range start frequency
—
—
–400. to 400. (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.00
0.00
0.00
✘ ✔
Output frequency corresponding to the bipolar
voltage input range starting point
A112
[O2]–[L] input active range end frequency
—
—
–400. to 400. (Hz);
model -4000HFx2 is
0.00 to 120.0 (Hz)
0.00
0.00
0.00
✘ ✔
Output frequency corresponding to the bipolar
voltage input range ending point
A113
[O2]–[L] input active range start voltage
—
—
–100 to 100 (%)
-100.
-100.
-100.
✘ ✔
Starting point for the bipolar voltage input range
A114
[O2]–[L] input active range end voltage
—
—
–100 to 100 (%)
100.
100.
100.
✘ ✔
Ending point for the bipolar voltage input range
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
A141
A input select for Calculate
Function
REM
00
Digital operator (A020/A220/A320)
02
02
02
✘ ✔
VR
0 1
Keypad potentiometer
O
02
[O] input
OI
03
[OI] input
COM
04
Comm. port
OP1
05
Expansion card 1
OP2
06
Expansion card 2
PLS
07
Pulse train frequency train input
A142
B input select for Calculate
Function
REM
00
Digital operator (A020/A220/A320)
03
03
03
✘ ✔
VR
0 1
Keypad potentiometer
O
02
[O] input
OI
03
[OI] input
COM
04
Comm. port
OP1
05
Expansion card 1
OP2
06
Expansion card 2
PLS
07
Pulse train frequency train input