Overload
Restriction
The inverter constantly monitors the motor current during acceleration, deceleration, and
constant speed. If the inverter reaches the overload restriction level, it adjusts the output
frequency automatically to limit the amount of overload. This function prevents an over-current
trip by inertia during rapid acceleration or large changes in load at constant speed. It also
attempts to prevent an over-voltage trip on deceleration due to regeneration. It accomplishes
this by temporarily suspending deceleration and/or increasing the frequency in order to dissi-
pate regenerative energy. Once the DC bus voltage falls sufficiently, deceleration will resume.
OLR Parameter Selection
– Two sets of overload restriction parameter settings and values are
available as outlined in the table below.
Use the B021—B026 group of settings to configure the two set of parameters as needed. By
assigning the Overload Restriction function [OLR] to an intelligent terminal, you can select the
set of restriction parameters that is in effect.
Note the following:
• If the overload restriction constant (B023 or B026) is set too short, an over-voltage trip
during deceleration will occur due to regenerative energy from the motor.
• When an overload restriction occurs during acceleration, the motor will take longer to reach
the target frequency, or may not reach it. The inverter will make the following adjustments:
a) Increase the acceleration time
b) Raise torque boost
c) Raise overload restriction level
Opt. Code
39
Symbol
[OLR]
Valid for
Inputs
[1] to [8]
Required
Settings
B021 – B023
(Set 1),
B024 – B026
(Set 2)
Default
terminal
Requires
config.
Symbol
Function Name
Input
State
Description
OLR
Overload Restriction
Selection
ON
Selects Overload Restriction Set 2,
B024, B025, B026 settings in effect
OFF
Selects Overload Restriction Set 1,
B021, B022, B023 settings in effect
Function
Function Code
Data or Range
Description
Set 1
Set 2
Overload Restriction
Operation Mode
B021
B024
00
Disable
01
Enabled during accel
and constant speed
02
Enabled during constant
speed
03
Enabled during accel,
constant speed, and
decel
Overload Restriction
Setting
B022
B025
Rated current * 0.5
to rated current * 2
Current value at which
the restriction begins
Deceleration Rate at
Overload Restriction
B023
B026
0.1 to 30 seconds
Deceleration time when
overload restriction
operates