Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–58
Logic Output
Signals
The Logic Output Function uses the inverter’s built-in logic feature. You can select any two of
the other intelligent output options for use as internal inputs to the logic function. You may also
select from three logical operators AND, OR, or XOR (exclusive OR), to be applied to the two
inputs. A total of six outputs are available, shown in the following tables.
The example below shows a configuration for [LOG1] Logic Output 1. Parameters C142 and
C143 contain option codes for two outputs we select to be used as inputs to the logic operation.
Parameter C144 contains the select code for the logic operation. 00=AND, 01=OR, and
02=OR.
Capacitor Life
Warning
The inverter calculates the capacitor life remaining based on the internal temperature of the
inverter and the cumulative power-ON time. The [WAC] Capacitor Life Warning output turns
ON to indicate that the capacitors have reached end-of-life. If this event occurs, Hitachi
recommends that you replace the main circuit board and logic circuit board. You may also use
monitor parameter D022 at the digital operator to monitor the status of capacitor life.
Opt. Code
and
Symbol
33=[LOG1]
34=[LOG2]
35=[LOG3]
36=[LOG4]
37=[LOG5]
38=[LOG6]
Valid for
Outputs
[11 to [15],
[ALx]
Required
Settings
C142 to
C159
Default
terminal
Requires
config.
Symbol
Option
Code
Function
A Input
B Input
Logical Operator
LOG1
33
Logic Output 1
C142
C143
C144
LOG2
34
Logic Output 2
C145
C146
C147
LOG3
35
Logic Output 3
C148
C149
C150
LOG4
36
Logic Output 4
C151
C152
C153
LOG5
37
Logic Output 5
C154
C155
C156
LOG6
38
Logic Output 6
C157
C158
C159
Input States
[LOGx] Output State
A Input
B Input
AND (00)
OR (01
XOR (02)
0
0
0
0
0
0
1
0
1
1
1
0
0
1
1
1
1
1
1
0
C142
A input
B input
Logic function
AND, OR, XOR
[LOG1]
Intelligent outputs used as internal
inputs: RUN, FA1, FA2, OL, OD, etc.:
C143
C144
[RUN] = option code 00
[FA2] = option code 02
Opt. Code
39
Symbol
[WAC]
Valid for
Outputs
[11 to [15],
[ALx]
Monitor
Settings
D022
Default
terminals
Requires
config.