ModBus Data Listing
Append
ix
B
B–60
Holding Registers, “C” Group Intelligent Terminal Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
C001
— Terminal [1] function
R/W
See
“Input Terminal
Configuration” on
page 3–50
1401h
05121
1 to 9,
11 to 18,
20 to 24,
26 to 29,
31 to 48,
no
—
C002
— Terminal [2] function
R/W
1402h
05122
C003
— Terminal [3] function
R/W
1403h
05123
C004
— Terminal [4] function
R/W
1404h
05124
C005
— Terminal [5] function
R/W
1405h
05125
C006
— Terminal [6] function
R/W
1406h
05126
C007
— Terminal [7] function
R/W
1407h
05127
C008
— Terminal [8] function
R/W
1408h
05128
—
(Reserved)
—
—
1409h
05129
—
—
—
(Reserved)
—
—
140Ah
05130
—
—
C011
— Terminal [1] active state
R/W
Select logic convention, two
option codes:
00..Normally open (N.O.)
01..Normally closed (N.C.)
140Bh
05131
0, 1
—
C012
— Terminal [2] active state
R/W
140Ch
05132
C013
— Terminal [3] active state
R/W
140Dh
05133
C014
— Terminal [4] active state
R/W
140Eh
05134
C015
— Terminal [5] active state
R/W
140Fh
05135
C016
— Terminal [6] active state
R/W
1410h
05136
C017
— Terminal (7) active state
R/W
1411h
05137
C018
— Terminal [8] active state
R/W
1412h
05138
C019
— Terminal [FW] active state
R/W
1413h
05139
—
(Reserved)
—
—
1414h
05140
—
—
C021
— Terminal [11] function
R/W
See
“Output Terminal
Configuration” on
page 3–55
1415h
05141
0 to 13,
19 to 26
—
C022
— Terminal [12] function
R/W
1416h
05142
C023
— Terminal [13] function
R/W
1417h
05143
C024
— Terminal [14] function
R/W
1418h
05144
C025
— Terminal [15] function
R/W
1419h
05145
C026
— Alarm relay terminal
function
R/W
141Ah
05146
C027
— [FM] signal selection
R/W
See
“Output Terminal
Configuration” on
page 3–55
141Bh
05147
0 to 10, 12
—
C028
— [AM] signal selection
R/W
141Ch
05148
C029
— [AMI] signal selection
R/W
141Dh
05149
C030
— Digital current monitor
reference value
R/W
Current with digital current
monitor output at 1.44 kHz
141Eh
05150
200 to
2000
0.1 %
C031
— Terminal [11] active state
R/W
Select logic convention, two
option codes:
00..Normally open (N.O.)
01..Normally closed (N.C.)
141Fh
05151
0, 1
—
C032
— Terminal [12] active state
R/W
1420h
05152
C033
— Terminal [13] active state
R/W
1421h
05153
C034
— Terminal [14] active state
R/W
1422h
05154
C035
— Terminal [15] active state
R/W
1423h
05155
C036
— Alarm relay active state
R/W
1424h
05156