ModBus Data Listing
Append
ix
B
B–48
A261
H Frequency upper limit
setting, 2nd motor
R/W
Sets a limit on output
frequency less than the
maximum frequency (A004)
224Fh
08783
0, 50 to
40000
0.01 Hz
A261
L
R/W
2250h
08784
A062
H Frequency lower limit
setting
R/W
Sets a limit on output
frequency greater than zero
1251h
04689
0, 50 to
40000
0.01 Hz
A062
L
R/W
1252h
04690
A262
H Frequency lower limit
setting, 2nd motor
R/W
Sets a limit on output
frequency greater than zero
2251h
08785
0, 50 to
40000
0.01 Hz
A262
L
R/W
2252h
08786
—
— (Reserved)
—
—
2253h
to
226Eh
08787
to
08814
—
—
A063
H Jump (center) frequency
setting
R/W
Up to 3 output frequencies
can be defined for the output
to jump past to avoid motor
resonances (center freq.)
1253h
04691
0 to 40000
0.01 Hz
A063
L
R/W
1254h
04692
A064
— Jump (hysteresis)
frequency width setting
R/W
Defines the distance from the
center frequency at which the
jump occurs
1255h
04693
0 to 1000
0.01 Hz
A065
H Jump (center) frequency
setting
R/W
Up to 3 output frequencies
can be defined for the output
to jump past to avoid motor
resonances (center freq.)
1256h
04694
0 to 40000
0.01 Hz
A065
L
R/W
1257h
04695
A066
— Jump (hysteresis)
frequency width setting
R/W
Defines the distance from the
center frequency at which the
jump occurs
1258h
04696
0 to 1000
0.01 Hz
A067
H Jump (center) frequency
setting
R/W
Up to 3 output frequencies
can be defined for the output
to jump past to avoid motor
resonances (center freq.)
1259h
04697
0 to 40000
0.01 Hz
A067
L
R/W
125Ah
04698
A068
— Jump (hysteresis)
frequency width setting
R/W
Defines the distance from the
center frequency at which the
jump occurs
125Bh
04699
0 to 1000
0.01 Hz
A069
H Acceleration stop
frequency setting
R/W
0.00 to 400.0 (Hz)
125Ch
04700
0 to 40000
0.01 Hz
A069
L
R/W
125Dh
04701
A070
— Acceleration stop time
frequency setting
R/W
0.0 to 60.0 (seconds)
125Eh
04702
0 to 600
0.1 sec.
A071
— PID Function Enable
R/W
00..PID operation OFF
01..PID operation ON
02..PID operation ON with
inverted output
125Fh
04703
0, 1, 2
—
A072
— PID proportional gain
R/W
0.2 to 5.0
1260h
0474
2 to 50
0.2
A073
— PID integral time constant
R/W
0.0 to 999.9, 1000. to 3600.
(seconds)
1261h
04705
0 to 36000
0.1 sec.
A074
— PID derivative gain
R/W
0.0 to 99.99, 100.0 (seconds)
1262h
04706
0 to 10000 0.01 sec.
A075
— PV scale conversion
R/W
0.01 to 99.99, 100.0
(seconds)
1263h
04707
1 to 9999
0.01
Holding Registers, “A” Group Standard Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.