SJ700
2
Inverter
Appendix B
B–55
B029
— Scan time constant for
active freq. matching
R/W
10 to 3000
131Eh
04894
0.01 sec.
0.01 sec.
B030
— Restart freq. select for
active freq. matching
R/W
00 .Frequency at last shutoff
01 .Maximum frequency
02 .Set frequency
131Fh
04895
B031
— Software lock mode selec-
tion
R/W
00 .Low-level access, [SFT]
input blocks all edits
01 .Low-level access, [SFT]
input blocks edits (except
F001 and Multi-speed
parameters)
02 .No access to edits
03 .No access to edits except
F001 and Multi-speed
parameters
10 .High-level access,
including B031
1320h
04896
—
(Reserved)
—
—
1321h
04897
—
—
—
(Reserved)
—
—
1322h
04898
—
—
B034
H Run/power-on warning
time
R/W
0 to 9999. (0 to 99990), 1000 to
6553 (10000 to 655300) (hours)
1323h
04899
0 to 65535
1 [10-
hours]
B034
L
R/W
1324h
04900
B035
— Rotational direction
restriction
R/W
00 .Enable for fwd. and rev.
01 .Enable for forward only
02 .Enable for reverse only
1325h
04901
0, 1, 2
—
B036
— Reduced voltage start
selection
R/W
000 (short) to 255 (long)
1326h
04902
0 to 255
—
B037
— Function code display
restriction
R/W
00 .Display all
01 .Display only utilized
functions
02 .Display user-selected
functions only
03 .Data comparison display
04 .Basic display
1327h
04903
0 to 4
—
B038
— Initial display selection
R/W
00 .Last value dislayed when
STR key was pressed
01 .D001
02 .D002
03 .D003
04 .D007
05 .F001
1328h
04904
0 to 5
—
B039
— Automatic user parameter
function enable
R/W
00 .Disable
01 .Enable
1329h
04905
0, 1
—
B040
— Torque limit selection
R/W
00 .4-quadrant mode
01 .Selected by two input
terminals
02 .From analog [O2] input
03 .From expansion card 1
04 .From expansion card 2
132Ah
04906
0 to 4
—
B041
— Torque limit (1) (forward-
driving in 4-quadrant
mode)
R/W
0. to 200. (%), no (disable torque
limit)
132Bh
04907
0 to 200,
255= (no)
1 %
Holding Registers, “B” Group Fine Tuning Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.