SJ700
2
Inverter
Appendix B
B–61
—
(Reserved)
—
—
1425h
05157
—
—
C038
— Low current indication
output mode select
R/W
00 . Output during accel/
decel and constant speed
01 . Output only during
constant speed
1426h
05158
0, 1
—
C039
— Low current indication
detection level
R/W
0.0 to 2.0 x rated inverter
current
1427h
05159
0 to 1800
0.1 %
C040
— Overload signal output
mode
R/W
00 . During accel / decel /
constant speed
01 . During constant speed
1428h
05160
0, 1
—
C041
— Overload level setting
R/W
0.00 x rated current to 2.00 x
rated current (A)
1429h
05161
0 to 1800
0.1 %
C042
H Frequency arrival setting
for accel.
R/W
Sets the frequency arrival
setting threshold for the
output frequency during
acceleration
142Ah
05162
0 to 40000
0.01 Hz
C042
L
R/W
142Bh
05163
C043
H Arrival frequency setting
for decel.
R/W
Sets the frequency arrival
setting threshold for the
output frequency during
deceleration
142Ch
05164
0 to 40000
0.01 Hz
C043
L
R/W
142Dh
05165
C044
— PID deviation level setting
R/W
Sets the PID loop error
threshold |SP - PV| (absolute
value) to trigger intelligent
output [OD]
142Eh
05166
0 to 1000
0.1 %
C045
H Frequency arrival setting
for acceleration (2)
R/W
0.0 to 99.99,
100.0 to 400.0 (Hz)
142Fh
05167
0 to 40000
0.01 Hz
C045
L
R/W
1430h
05168
C046
H Frequency arrival setting
for deceleration (2)
R/W
0.0 to 99.99,
100.0 to 400.0 (Hz)
1431h
05169
0 to 40000
0.01 Hz
C046
L
R/W
1432h
05170
—
(Reserved)
—
—
1433h
to
1437h
05171
to
05175
—
—
C052
— Maximum PID feedback
(PV) data
R/W
0.0 to 100.0 (%)
1438h
05176
0 to 1000
0.1 %
C053
— Minimum PID feedback
(PV) data
R/W
0.0 to 100.0 (%)
1439h
05177
0 to 1000
0.1 %
—
(Reserved)
—
—
143Ah
05178
C055
— Over-torque (forward-
driving) level setting
R/W
Threshold for intelligent
output terminal [OTQ],
quadrant I
143Bh
05179
0 to 180
1 %
C056
— Over-torque (reverse
regenerating) level setting
R/W
Threshold for intelligent
output terminal [OTQ],
quadrant II
143Ch
05180
0 to 180
1 %
C057
— Over-torque (reverse
driving) level setting
R/W
Threshold for intelligent
output terminal [OTQ],
quadrant III
143Dh
05181
0 to 180
1 %
C058
— Over-torque (forward
regenerating) level setting
R/W
Threshold for intelligent
output terminal [OTQ],
quadrant IV
143Eh
05182
0 to 180
1 %
Holding Registers, “C” Group Intelligent Terminal Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.