SJ700
2
Inverter
Appendix B
B–57
B064
— [OI] input min. limit level
of window comparator
R/W
0. to 100. (%)
Lower limit = B063 – B066 / 2
1343h
04931
0 to 100
1 %
B065
— [OI] input hysteresis width
of window comparator
R/W
0. to 10. (%)
Lower limit = B063 – B064 / 2
1344h
04932
0 to 10
1 %
B066
— [O/OI/O2] input maximum
limit level of window
comparator
R/W
–100. to 100. (%)
Lower limit = B067 + B068 / 2
1345h
04933
0 to 100
1 %
B067
— [O/OI/O2] input minimum
limit level of window
comparator
R/W
–100. to 100. (%)
Lower limit = B066 – B068 / 2
1346h
04934
0 to 100
1 %
B068
— [O/OI/O2] input hysteresis
width of window
comparator
R/W
0. to 10. (%)
Lower limit = B066 – B067 / 2
1347h
04935
0 to 10
1 %
—
(Reserved)
—
—
1348h
04936
—
—
B070
— [O] input disconnect
threshold
R/W
0 to 100 (%);
255 = ignore setting
1349h
04937
0 to 100,
255
1 %
B071
— [OI] input disconnect
threshold
R/W
0 to 100 (%);
255 = ignore setting
134Ah
04938
0 to 100,
255
1 %
B072
— [O2] input disconnect
threshold
R/W
0 to 100 (%);
255 = ignore setting
134Bh
04939
0 to 100,
255
1 %
—
(Reserved)
—
—
134Ch
to
1350h
04940
to
04944
—
—
B078
— Clear cumulative input
power data
R/W
00 .No change
01 .Clear the data
1351h
04945
0, 1
—
B079
— Cumulative input power
display gain setting
R/W
1. to 1000.
1352h
04946
1 to 1000
1
—
(Reserved)
—
—
1353h
04947
—
—
—
(Reserved)
—
—
1354h
04948
—
—
B082
— Start frequency adjustment
R/W
0.10 to 9.99 (Hz)
1355h
04949
10 to 999
0.01 Hz
B083
— Carrier frequency setting
R/W
Sets the PWM carrier (internal
switching frequency)
1356h
04950
5 to 150
0.1 kHz
B084
— Initialization mode
(parameters or trip history)
R/W
00 .Trip history clear
01 .Parameter initialization
02 .Trip history clear and
parameter initialization
1357h
04951
0, 1, 2
—
B085
— Country code for initializa-
tion
R/W
00 .Japan version
01 .Europe version
02 .USA version
1358h
04952
0, 1, 2
—
B086
— Frequency scaling conver-
sion factor
R/W
Specify a constant to scale D007
to display in engineering units
1359h
04953
1 to 999
0.1
B087
— STOP key enable
R/W
00 .Enable
01 .Disable
02 .Disable only the STOP
function
135Ah
04954
0, 1, 2
—
Holding Registers, “B” Group Fine Tuning Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.