SJ700
2
Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–53
29
UDC
Remote Control Data
Clearing
Clears the UP/DWN frequency memory by forcing it to equal
the set frequency parameter F001. Setting C101 must be
set=00 to enable this function to work.
31
OPE
Operator Control
Forces the source of the output frequency setting (A001) and
the RUN command (A002) to be from the digital operator
(F001 and the Run key, respectively)
32
SF1
Multi-speed bit 1
Multiple speed select, Bit 1
33
SF2
Multi-speed bit 2
Multiple speed select, Bit 2
34
SF3
Multi-speed bit 3
Multiple speed select, Bit 3
35
SF4
Multi-speed bit 4
Multiple speed select, Bit 4
36
SF5
Multi-speed bit 5
Multiple speed select, Bit 5
37
SF6
Multi-speed bit 6
Multiple speed select, Bit 6
38
SF7
Multi-speed bit 7
Multiple speed select, Bit 7
39
OLR
Overload restriction
Turn ON to select current overload parameter set 2
(B024, B025, B026); OFF selects set 1(B021, B022, B023)
40
TL
Torque limit enable
ON enables torque limit feature; OFF disables all torque limit
sources and defaults to 200% of inverter rated torque output
41
TRQ1
Torque limit selection, bit
1
Binary encoded torque limit select, Bit 1 (LSB)
42
TRQ2
Torque limit selection, bit
2
Binary encoded torque limit select, Bit 2 (MSB)
43
PPI
Proportional /
Proportional/Integral
mode selection
ON selects Proportional-only control; OFF selects Propor-
tional-Integral control
44
BOK
Brake confirmation signal
Indicates external brake has released (used only for external
brake control function)
45
ORT
Orientation (home search) The encoder is in the home (oriented) position
46
LAC
LAC: LAD cancel
Disables the normal Linear Accel / Decel (LAD) mode
47
PCLR
Position deviation reset
Clears the position deviation by setting the actual position
equal to the desired position
48
STAT
Pulse train position
command input enable
Enables the pulse train control of motor
50
ADD
Add frequency enable
Adds the A145 value (Add Frequency) to the output
frequency
51
F-TM
Force terminal mode
Force inverter to use input terminals for output frequency and
Run command sources
52
ATR
Torque control enable
Inverter operates by controlling torque instead of speed
53
KHC
Clear cumulative power
value
Clears cumulative power data displayed by parameter D015
54
SON
Speed servo ON
Enables the inverter to accept FW/REV commands; for use
with V/F curve
vector control with sensor
(A044=05)
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description