SJ700
2
Inverter
Appendix B
B–47
—
(Reserved)
—
—
323Fh
to
326Ch
12863
to
12908
—
—
A045
— V/f gain setting
R/W
Sets voltage gain of the
inverter
123Fh
04671
20 to 200
1 %
A046
— Automatic torque boost
voltage gain
R/W
Voltage compensation gain
for automatic torque boost
1240h
04672
0 to 255
1
A246
— Automatic torque boost
voltage gain, 2nd motor
R/W
Voltage compensation gain
for automatic torque boost
2240h
08768
0 to 255
1
A047
— Automatic torque boost
slip gain
R/W
Slip compensation gain for
automatic torque boost
1241h
04673
0 to 255
1
—
(Reserved)
—
—
1242h
to
1244h
04674
to
04676
—
—
A247
— Automatic torque boost
slip gain, 2nd motor
Slip compensation gain for
automatic torque boost
2241h
08769
0 to 255
1
—
(Reserved)
—
—
2242h
to
224Eh
08770
to
08782
—
—
A051
— DC braking enable
R/W
00 . Disable
01 . Enable
02 . Brake at set frequency
only
1245h
04677
0, 1, 2
—
A052
— DC braking frequency
setting
R/W
Frequency at which DC
braking activates during
decel.
1246h
04678
0 to 40000
0.01 Hz
A053
— DC braking wait time
R/W
The delay after reaching the
DC braking frequency, or
[DB] signal, before DC
braking begins
1247h
04679
0 to 50
0.1 sec.
A054
— DC braking force during
deceleration
R/W
Variable DC braking force
1248h
04680
0 to 80
1 %
A055
— DC braking time for decel-
eration
R/W
Sets the duration for DC
braking during decel
1249h
04681
0 to 600
0.1 sec.
A056
— DC braking / edge or level
detection for [DB] input
R/W
00 . Edge detection
01 . Level detection
124Ah
04682
0, 1
—
A057
— DC braking force for
starting
R/W
Variable DC braking force
124Bh
04683
0 to 80
1 %
A058
— DC braking time for
starting
R/W
Sets the duration for DC
braking before accel.
124Ch
04684
0 to 600
0.1 sec.
A059
— DC braking carrier
frequency setting
R/W
0.5 to 15 (kHz) for models
up to –550xxx, 0.5 to 10
(kHz) for 750xxx to 1500xxx
models
124Dh
04685
5 to 150;
5 to 100
0.1 kHz
—
(Reserved)
—
—
124Eh
04686
—
—
A061
H Frequency upper limit
setting
R/W
Sets a limit on output
frequency less than the
maximum frequency (A004)
124Fh
04687
0, 50 to
40000
0.01 Hz
A061
L
1250h
04688
Holding Registers, “A” Group Standard Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.