“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–54
55
FOC
Current forcing
Forces excitation current in motor at 0 speed; for use with V/f
curve settings A044/A244 = 03, 04, and 05
56
MI1
General-purpose input 1
Easy sequence function, general input 1
57
MI2
General-purpose input 2
Easy sequence function, general input 2
58
MI3
General-purpose input 3
Easy sequence function, general input 3
59
MI4
General-purpose input 4
Easy sequence function, general input 4
60
MI5
General-purpose input 5
Easy sequence function, general input 5
61
MI6
General-purpose input 6
Easy sequence function, general input 6
62
MI7
General-purpose input 7
Easy sequence function, general input 7
63
MI8
General-purpose input 8
Easy sequence function, general input 8
65
AHD
Analog holding command Causes the inverter to sample and hold the analog speed input,
maintaining constant speed while this signal is ON
66
CP1
Multi-stage position
select 1
Binary-encoded position select, bit 1 (LSB)
67
CP2
Multi-stage position
select 2
Binary-encoded position select, bit 2 (LSB)
68
CP3
Multi-stage position
select 3
Binary-encoded position select, bit 3 (MSB)
69
ORL
Zero-return limit function
Indicates that the load has reached the zero-return point, so
the inverter stops the zero-return operation in progress
70
ORG
Zero-return trigger
function
Starts a zero-return operation (load moves toward the zero-
return point)
71
FOT
Forward drive stop
Limits the forward rotational torque to 10%; for use at the end
of travel in position control mode
72
ROT
Reverse drive stop
Limits the reverse rotational torque to 10%; for use at the end
of travel in position control mode
73
SPD
Speed/position control
select
Causes the inverter to perform only speed control (ignores
encoder pulses) while in position control mode
74
PCNT
Pulse counter input
Pulse counter input
75
PCC
Pulse counter clear
Clears the pulse count
no
—
Not selected
(input ignored)
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description