“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–56
Output Summary Table
- This table shows all twenty-two functions for the logic output
terminals [11] – [15] at a glance. Detailed function descriptions, related parameters, settings,
and example wiring diagrams are in
“Using Intelligent Output Terminals” on page 4–43
.
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
00
RUN
Run signal
Inverter is in Run Mode, motor running
01
FA1
Frequency arrival type 1 –
constant speed
When output to motor is at the standard set frequency F001
02
FA2
Frequency arrival type 2 –
over-frequency
Turns ON when output to motor is at or above the FA
Threshold 1 (C042) during accel; turns OFF when motor
output goes below the threshold during decel
03
OL
Overload advance notice
signal (1)
Output current is more than the set Threshold 1 for the
overload signal (set with C041)
04
OD
Output deviation for PID
control
PID error is more than the set threshold for the deviation
signal
05
AL
Alarm signal
Alarm condition has been met and not reset
06
FA3
Frequency arrival type 3 –
at frequency
Output to motor is at the FA Threshold 1 (C042) during accel,
or at C043 during decel
07
OTQ
Over-torque signal
Over-torque feature is enabled and the motor is generating
excess torque
08
IP
Instantaneous power
failure signal
Inverter input power has decreased below the acceptable input
voltage level
09
UV
Under-voltage signal
Inverter input power has decreased below the acceptable input
voltage level
10
TRQ
In torque limit
Output torque exceeds level set for the particular torque/
frequency quadrant in effect during operation
11
RNT
Operation time over
Inverter Run time exceeds the limit set by Run/power-on
warning time (B034)
12
ONT
Plug-in time over
Inverter plug-in time exceeds the set limit
13
THM
Thermal alarm signal
Thermal limit for the motor is exceeded
19
BRK
Brake release signal
ON when the inverter signals the external braking system to
release (open) its brake; OFF when the inverter is not driving
the motor and needs the external brake engaged
20
BER
Brake error signal
ON when the output current is less than the set releasing
current; OFF when the braking function is not in use, or when
the output current to the motor is correct and it is safe to
release the brake
21
ZS
Zero speed detect
Encoder pulses of the motor have stopped
22
DSE
Speed deviation
maximum
Velocity error exceeds the error threshold defined for the
encoder input
23
POK
Positioning completion
Load position is at the target
24
FA4
Frequency arrival type 4 –
over-frequency (2)
ON when output to motor is at or above the FA threshold 2
(C045) during accel; OFF when the output to motor is below
the FA threshold 2 (C046) during decel
25
FA5
Frequency arrival type 5 –
at frequency (2)
Output to motor is at the FA threshold 2 (C045) during accel
or at C046 during decel