“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–58
Analog Summary Table
- The following tables show all functions available for assignment to
the three analog output terminals [FM], [AM], [AMI] at a glance. Detailed descriptions, related
parameters, and settings are in
“Analog Output Operation” on page 4–66
.
56
WCO2
[O2] terminal window
comparator
[O2] input is within comparator window set by B066 and
B067
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
C027 Setting for Terminal FM
Option
Code
Function Name
Description
Corresponding Signal
Range
00
Output frequency
Actual motor speed, represented by PWM
signal
0 to max. frequency in Hz
01
Output current
Motor current (% of maximum rated output
current), represented by PWM signal
0 to 200%
02
Output torque
Rated output torque
0 to 200%
03
Digital output
frequency
Output frequency (available only at FM
output)
0 to max. frequency in Hz
04
Output voltage
Rated output voltage to motor
0 to 100%
05
Input power
Rated input power
0 to 200%
06
Electronic thermal
overload
Percentage of electronic overload attained
0 to 100%
07
LAD frequency
Internal ramp generator frequency
0 to max. frequency in Hz
08
Digital current monitor
Signal freq. = 1,440 Hz when
output current = C030 setting
0.2 x rated current to 2.0 x
rated current (A)
09
Motor temperature
Thermistor input temp. reading in PWM
format
0 to 200°C
10
Heat sink temperature
Inverter heatsink temp. reading in PWM
format
0 to 200°C
12
General YA(0) analog
output
Internal analog value from EZ-Sequence
0 to 100%
C028 Setting for Terminal [AM]; C029 Setting for Terminal [AMI]
Option
Code
Function Name
Description
Corresponding Signal
Range
00
Output frequency
Actual motor speed, represented by PWM
signal
0 to max. frequency in Hz
01
Output current
Motor current (% of maximum rated output
current), represented by PWM signal
0 to 200%
02
Output torque
Rated output torque
0 to 200%
03
Digital output
frequency
Output frequency (available only at FM
output)
0 to max. frequency in Hz
04
Output voltage
Rated output voltage to motor
0 to 100%