ModBus Data Listing
Append
ix
B
B–62
—
(Reserved)
—
—
143Fh
05183
—
—
—
(Reserved)
—
—
1440h
05184
—
—
C061
— Electronic thermal warning
level setting
R/W
Sets the threshold for
intelligent output [THM]
1441h
05185
0 to 100
1 %
C062
— Alarm code output
R/W
00..Disable
01..Enable – 3-bit code
02..Enable – 4-bit code
1442h
05186
0, 1, 2
—
C063
— Zero speed detection level
R/W
0.00 to 99.99 / 100.0 (Hz)
1443h
05187
0 to 10000
0.01 Hz
C064
— Heatsink overheat warning
level
R/W
Alarm temperature thresh-
old for heatsink in inverter
1444h
05188
0 to 200
1 °C
—
(Reserved)
—
—
1445h
to
144Ah
05189
to
05194
—
—
C071
— Communication speed
selection
R/W
02..Test
03..2400 (bps)
04..4800 (bps)
05..9600 (bps)
06..19200 (bps)
144Bh
05195
2 to 6
—
C072
Node allocation
R/W
Set the address of the
inverter on the network
144Ch
05196
1 to 32
—
C073
— Communication data
length selection
R/W
07..7-bit data
08..8-bit data
144Dh
05197
7, 8
bits
C074
Communication parity
selection
R/W
00..No parity
01..Even parity
02..Odd parity
144Eh
05198
0, 1, 2
—
C075
— Communication stop bit
selection
R/W
01..1 Stop bit
02..2 Stop bits
144Fh
05199
1, 2
bits
C076
— Action upon communica-
tion error selection
R/W
00..Trip
01..Trip after deceleration
and stop
02..No action (ignore errors)
03..Free-run stop
04..Decelerate and stop
1450h
05200
0 to 4
—
C077
— Communication timeout
before trip
R/W
0.00 to 99.99 (seconds)
1451h
05201
0 to 9999
0.01 sec.
C078
— Communication wait time
R/W
Time the inverter waits after
receiving a message before it
transmits
1452h
05202
0 to 1000
1 msec.
C079
— Communication protocol
select
R/W
00..ASCII
01..ModBus RTU
1453h
05203
0, 1
—
—
(Reserved)
—
—
1454h
05204
—
—
C081
— [O] input span calibration
R/W
0. to 9999., 1000 to 6553
(10000 to 65530)
1455h
05205
0 to 65530
1
C082
— [OI] input span calibration
R/W
0. to 9999., 1000 to 6553
(10000 to 65530)
1456h
05206
0 to 65530
1
C083
— [O2] input span calibration
R/W
0. to 9999., 1000 to 6553
(10000 to 65530)
1457h
05207
0 to 65530
1
—
(Reserved)
—
—
1458h
05208
—
—
Holding Registers, “C” Group Intelligent Terminal Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.