Output Terminal
Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the table
below.
NOTE:
*Terminals [11] – [13] or [11] – [14] are automatically configured as AC0 – AC2 or
AC0 – AC3 when C62 is configured to enable alarm code output.
The output logic convention is programmable for terminals [11] – [15], and the alarm relay
terminals. The open-collector output terminals [11] – [15] default to normally open (active
low), but you can select normally closed (active high) for the terminals in order to invert the
sense of the logic. You can invert the logical sense of the alarm relay output as well.
Func.
Code
Name/
Description
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C021
Terminal [11] function *
51 programmable functions
available for logic
(discrete) outputs (see next
section)
01 [FA1]
01 [FA1]
01 [FA1]
✘ ✔
C022
Terminal [12] function *
00 [RUN]
00 [RUN]
00 [RUN]
✘ ✔
C023
Terminal [13] function *
03 [OL]
03 [OL]
03 [OL]
✘ ✔
C024
Terminal [14] function *
07 [OTQ]
07 [OTQ]
07 [OTQ]
✘ ✔
C025
Terminal [15] function
08 [IP]
08 [IP]
08 [IP]
✘ ✔
C026
Alarm relay terminal
function
05 [AL]
05 [AL]
05 [AL]
✘ ✔
C027
[FM] signal selection
12 programmable functions
available for analog outputs
(see after next section)
00 (output freq.)
✘ ✔
C028
[AM] signal selection
00 (output freq.)
✘ ✔
C029
[AMI] signal selection
00 (output freq.)
✘ ✔
C030
Digital current monitor
reference value
0.20 x rated current to 2.00
x rated current (A)
Rated current x 1.0
✔ ✔
Current with digital current monitor output at 1.44 kHz
✔ ✔
Func.
Code
Name/
SRW Display
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C031
Terminal [11] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
C032
Terminal [12] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
C033
Terminal [13] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
C034
Terminal [14] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
C035
Terminal [15] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
C036
Alarm relay terminal active
state
NO
00
Normally open (N.O.)
01
01
01
✘ ✔
NC
0 1
Normally closed (N.C.)