“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–60
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C038
Low current indication
output mode select
ON
00
Output during acceleration/deceleration and
constant speed operation
01
01
01
✘ ✔
CRT
0 1
Output only during constant speed
C039
Low current indication detection level
0.0 to 1.80 x rated inverter current
Rated current x 1.0
✘ ✔
Low current threshold, used for intelligent output [LOC]
✘ ✔
C040
Overload signal output mode
ON
00
During accel / decel / constant speed
01
01
01
✘ ✔
Choose when the overload
signal is enabled
CRT
0 1
During constant speed only
C041
Overload level setting 1
0.00 x rated current to 1.80 x rated current
(A)
Rated current for
inverter
✘ ✔
C042
Frequency arrival setting for acceleration
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
0.00
0.00
✘ ✔
Sets the frequency arrival setting threshold for the output frequency during acceleration
C043
Arrival frequency setting for deceleration
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
0.00
0.00
✘ ✔
Sets the frequency arrival setting threshold for the output frequency during deceleration
C044
PID deviation level setting
0.0 to 100.0 (%)
3.0
3.0
3.0
✘ ✔
Sets the PID loop error threshold |SP - PV| (absolute value) to trigger intelligent output [OD]
C045
Frequency arrival setting for acceleration (2)
0.0 to 99.99, 100.0 to 400.0 (Hz)
0.00
0.00
0.00
✘ ✔
C046
Frequency arrival setting for deceleration (2)
0.0 to 99.99, 100.0 to 400.0 (Hz)
0.00
0.00
0.00
✘ ✔
C052
Maximum PID feedback (PV) data
0.0 to 100.0 (%)
0.00
0.00
0.00
✘ ✔
C053
Minimum PID feedback (PV) data
0.0 to 100.0 (%)
100.0
100.0
100.0
✘ ✔
C055
Over-torque (forward-driving) level setting
0. to 180. (%)
100.
100.
100.
✘ ✔
Threshold for intelligent output terminal [OTQ], quadrant I
C056
Over-torque (reverse regenerating) level
setting
0. to 180. (%)
100.
100.
100.
✘ ✔
Threshold for intelligent output terminal [OTQ], quadrant II
C057
Over-torque (reverse driving) level setting
0. to 180. (%)
100.
100.
100.
✘ ✔
Threshold for intelligent output terminal [OTQ], quadrant III
C058
Over-torque (forward regenerating) level
setting
0. to 180. (%)
100.
100.
100.
✘ ✔
Threshold for intelligent output terminal [OTQ], quadrant IV
C061
Electronic thermal warning level setting
0. to 100. (%)
80.
80.
80.
✘ ✔
Sets the threshold for intelligent output [THM]
C062
Alarm code output
OFF
00
Disable
00
00
00
✘ ✔
Allows binary alarm codes to
be output to intelligent
terminals
3BIT
0 1
Enable – 3-bit code
4BIT
02
Enable – 4-bit code
C063
Zero speed detection level
0.00 to 99.99 / 100.0 (Hz)
0.00
0.00
0.00
✘ ✔
C064
Heatsink overheat warning level
0. to 200.0 (°C)
120
120
120
✘ ✔
Alarm temperature threshold for heatsink in inverter
✘ ✔