ASCII Mode Communications
Append
ix
B
B–14
Command – 06
The 06 command reads a single parameter
value from the inverter, which is specified by
the data field this read command.
The receive frame includes an ACK
(acknowledge) character, followed by an
8-byte data field.
Use the codes in the table below to return parameters for H003 and H203 (motor capacity
selection).
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
Command
Transmission command
2 bytes 06
Data
Parameter specified to be read
4 bytes (see tables below)
BCC
Block check sum code
2 bytes Exclusive OR of Node,
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
ACK
Control code (ACKnowledge)
1 byte
ACK (0x06)
Data
Parameter value
8 bytes Value of parameter times ten,
returned as ASCII char. code,
except for H003 and H203 (see
table below)
BCC
Block check sum code
2 bytes Exclusive OR of Node,
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
STX Node
Command
Data
BCC [CR]
Transmit frame format
STX Node
ACK
Data
BCC [CR]
Receive frame format
Code Data
00
01
02
03
04
05
06
07
08
09
10
Japan or U.S.A. mode (B85 = 00 or 02)
0.2 kW
—
0.4
—
0.75
—
1.5
2.2
—
3.7
—
EU mode (B85=01)
0.2 kW
0.37
—
0.55
0.75
1.1
1.5
2.2
3.0
—
4.0
Code Data
11
12
13
14
15
16
17
18
19
20
21
Japan or U.S.A. mode (B85 = 00 or 02)
5.5 kW
7.5
11
15
18.5
22
30
37
45
55
75
EU mode (B85=01)
5.5 kW
7.5
11
15
18.5
22
30
37
45
55
75
Code Data
22
23
24
25
26
27
28
29
30
31
32
Japan or U.S.A. mode (B85 = 00 or 02)
90 kW
110
132
150
160
185
200
220
250
280
300
EU mode (B85=01)
90 kW
110
132
150
160
185
200
220
250
280
300
Code Data
33
34
35
36
—
—
—
—
—
—
—
Japan or U.S.A. mode (B85 = 00 or 02) 315 kW
340
355
400
—
—
—
—
—
—
—
EU mode (B85=01)
315 kW
340
355
400
—
—
—
—
—
—
—