xiv
400V
100
75
SJ700–750HFU2/E
(All)
1/0 || 1/0
14.8
20.0
125
90
SJ700–900HFU2/E
(All)
1/0 || 1/0
14.8
20.0
150
110
SJ700–1100HFU2/E
(All)
3/0 || 3/0
25.8
35.0
150
132
SJ700–1320HFE2,
SJ700–1500HFU2
(All)
3/0 || 3/0
25.8
35.0
250
185
SJ700–1850HFU2/E
[R, S, T, U, V, W]
250 kcmil x 2
55.3
75.0
[P, PD, N]
300 kcmil x 2
6.0
8.1
[P, N] Braking unit
1
55.3
75.0
Earth GND
250 kcmil
28.9
39.2
400
315
SJ700–3150HFU2/E
[R, S, T, U, V, W]
400 kcmil x 2
32.5
44.0
[P, PD, N]
500 kcmil x 2
14.8
20
[P, N] Braking unit
250 kcmil
32.5
44.0
Earth GND
400 kcmil
28.9
39.2
500
400
SJ700–4000HFU2/E
[R, S, T, U, V, W]
600 kcmil x 2
38.4
52.0
[P, PD, N]
800 kcmil x 2
14.8
20
[P, N] Braking unit
250 kcmil x 2
38.4
52.0
Earth GND
600 kcmil
28.9
39.2
Input
Voltage
Motor
Output
400V
Inverter Model
Power Terminals
Wire Size Range (AWG)
Torque
HP
kW
ft-lbs
(N-m)