“P” Group: Expansion Card Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–70
P029
Motor gear ratio denominator setting
1 to 9999
1.
1.
1.
✘ ✔
P031
Accel/decel time input selec-
tion
REM
00
Inverter
00
00
00
✘ ✘
OP1
0 1
Expansion card 1
OP2
02
Expansion card 2
P032
Positioning command input
selection
REM
00
Inverter
00
00
00
✘ ✔
OP1
0 1
Expansion card 1
OP2
02
Expansion card 2
P033
Torque command input
selection
O
00
[O] terminal
00
00
00
✘ ✘
OI
0 1
[OI] terminal
O2
02
[O2] terminal
REM
03
Inverter keypad (P034)
P034
Torque command setting
0. to 180. (%)
0.
0.
0.
✘ ✘
P035
Torque command polarity
select
NOR
00
Indicated by signal polarity at [O2] terminal
00
00
00
✘ ✘
DIR
0 1
Depends on motor direction
P036
Torque bias mode
NO
00
Disable
00
00
00
✘ ✘
DIR
0 1
Inverter keypad (P037)
NOR
02
[O2] terminal input
P037
Torque bias value
0. to 180. (%)
0.
0.
0.
✘ ✘
P038
Torque bias polarity
NOR
00
Indicated by polarity
00
00
00
✘ ✔
DIR
0 1
Depends on motor direction
P039
Forward speed limit for torque-control mode
0.00 to maximum frequency (Hz)
0.00
0.00
0.00
✘ ✘
P040
Reverse speed limit for torque-control mode
0.00 to maximum frequency (Hz)
0.00
0.00
0.00
✘ ✘
P044
DeviceNet comm watchdog timer
0.00 to 99.99 (seconds)
1.00
1.00
1.00
✘ ✘
P045
Inverter action on DeviceNet
comm error
TRP
00
Trip
01
01
01
✘ ✘
FTP
0 1
Decelerate and trip
NO
02
Hold last speed
FRS
03
Free run stop
DEC
04
Decelerate and stop
P046
DeviceNet polled I/O: Output instance
number
20, 21, 100
21
21
21
✘ ✘
P047
DeviceNet polled I/O: Input instance number
70, 71, 101
71
71
71
✘ ✘
P048
Inverter action on DeviceNet
idle mode
TRP
00
Trip
01
01
01
✘ ✘
FTP
0 1
Decelerate and trip
NO
02
Hold last speed
FRS
03
Free run stop
DEC
04
Decelerate and stop
P049
DeviceNet motor poles
setting for RPM
poles
poles
00 to 38 (even numbers only)
0
0
0
✘ ✘
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)