The functions in the following table configure the signals for the analog output terminals. Note
that these settings do not change the current/voltage or sink/source characteristics – only the
zero and span (scaling) of the signals.
NOTE:
See additional settings for analog calibration: Parameter B080 [AM] Terminal Analog
Meter Adjustment (gain), parameter B081 [FM] Terminal Analog Meter Adjustment (gain).
NOTE:
Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter.
Do not change these settings unless absolutely necessary. Note that if you restore factory
defaults for all parameters, these settings will not change.
Miscellaneous
Functions
The following table contains miscellaneous functions not in other function groups.
C102/C103: Reset Mode / Restart Mode –
The reset mode selection, set via parameter C102,
determines how the inverter responds to the [RS] intelligent input signal or keypad Stop/Reset
key in a trip condition. The options allow you to cancel the trip on either the OFF-to-ON or
ON-to-OFF transition of [RS], and if desired, stop the inverter if it is in Run Mode. A trip event
causes the inverter output to the motor to turn OFF immediately. If in Run Mode when the trip
Func.
Code
Name/
Description
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C081
[O] input span calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
C082
[OI] input span calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
C083
[O2] input span calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
C085
Thermistor input tuning (gain)
0.0 to 999.9., 1000
105.0
105.0
105.0
✔ ✔
C121
[O] input zero calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
C122
[OI] input zero calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
C123
[O2] input zero calibration
0. to 9999., 1000 to 6553
(10000 to 65530)
Factory-calibrated
✔ ✔
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C091
Debug mode enable
MD0
00
No display
00
00
00
✘ ✘
MD1
0 1
Display
C101
Up/Down memory mode
selection
NO-STR
00
Clear last frequency (return to
default frequency F001)
00
00
00
✘ ✔
Controls speed setpoint for
the inverter after power cycle
STR
0 1
Keep last frequency adjusted by
UP/DWN