Output Function
Adjustment
Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The
overload level parameter (C041) sets the
motor current level at which the
overload signal [OL] turns ON. The
range of settings is from 0% to 200% of
the rated current for the inverter. This
function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are avail-
able on other functions).
The frequency arrival signal, [FA1] to
[FA5], is intended to indicate when the
inverter output has reached (arrived at)
the target frequency. You can adjust the
timing of the leading and trailing edges
of the signal via two parameters specific
to acceleration and deceleration ramps,
C042 and C043.
The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value)
and Process Variable (actual value). The
PID output deviation signal [OD]
(output terminal function option code
04) indicates when the error magnitude
has exceeded a magnitude you define.
05
Input power
Rated input power
0 to 200%
06
Electronic thermal
overload
Percentage of electronic overload attained
0 to 100%
07
LAD frequency
Internal ramp generator frequency
0 to max. frequency in Hz
09
Motor temperature
Thermistor input temp. reading in PWM
format
0 to 200°C
10
Heat sink temperature
Inverter heatsink temp. reading in PWM
format
0 to 200°C
13
General YA(1) analog
output
Internal analog value from EZ-Sequence
0 to 100% (output only from
terminal [AM])
14
General YA(2) analog
output
Internal analog value from EZ-Sequence
0 to 100% (output only from
terminal [AMI])
C028 Setting for Terminal [AM]; C029 Setting for Terminal [AMI]
Option
Code
Function Name
Description
Corresponding Signal
Range
Motor
current
Overload
signal
C041
t
1
0
Output
frequency
Arrival
signal
C042
C043
t
1
0
PID Error
(PV-SP)
Deviation
Signal
C044
t
1
0
SP